6-36
n097
Overtorque Detection
Function Selection 2
Register
0161
Hex
Changes during
operation
No
Setting
range
0, 1
Unit of
setting
1
Default setting
0
Set Values
Value
Description
0
Detects overtorque from output torque.
1
Detects overtorque from output current.
·
Set n097 to the item used for overtorque detection.
·
In V/f control mode, overtorque is detected through the output current of the Inverter
regardless of the set value.
n098
Overtorque Detection Level
Register
0162
Hex
Changes during
operation
No
Setting
range
30 to 200 (%)
Unit of
setting
1%
Default setting
160
Set Values
·
Set n098 to the type of overtorque detection level.
To detect the level through the output torque, set the torque in percentage based on
the rated motor torque as 100%.
To detect the level through the output current, set the current in percentage based on
the rated current of the Inverter as 100%.
n099
Overtorque Detection Time
Register
0163
Hex
Changes during
operation
No
Setting
range
0.1 to 10.0 (s)
Unit of
setting
0.1 s
Default setting
0.1
Set Values
·
Set the overtorque detection time.
·
The Inverter will detect overtorque when the current (or torque) the same as or higher
than the detection level is output for the preset detection time.
Advanced Operation
Chapter 6
Summary of Contents for SYSDRIVE 3G3MV A2002
Page 1: ...USER S MANUAL SYSDRIVE 3G3MV Multi function Compact Inverter Cat No I527 E2 02...
Page 15: ...Chapter 1 Overview 1 1 Function 1 2 Nomenclature 1 3 New Features 1...
Page 24: ...Chapter 2 Design 2 1 Installation 2 2 Wiring 2...
Page 89: ...Chapter 4 Test Run 4 1 Procedure for Test Run 4 2 Operation Example 4...
Page 286: ...Chapter 9 Specifications 9 1 Inverter Specifications 9 2 Option Specifications 9...
Page 311: ...Chapter 10 List of Parameters 10...
Page 342: ...Chapter 11 Using the Inverter for a Motor 11...
Page 348: ...Appendix A Standard Models...