5-27
5-7 Setting the Acceleration/Deceleration Time
The following description provides information on parameters related to
acceleration and deceleration time settings.
Trapezoidal and S-shape acceleration and deceleration are available.
Using the S-shape characteristic function for acceleration and decelera-
tion can reduce shock to the machinery when stopping or starting.
H
Acceleration/Deceleration Time Unit (n018)
·
The acceleration and deceleration time of the Inverter can be set within a range from
0.0 to 6,000 s without changing the default setting. If a more precise unit of setting is
required, this parameter can be set for 0.01-s increments. In this case, the setting
range will be from 0.00 to 600.0 s.
n018
Acceleration/Deceleration
Time Setting
Register
0112
Hex
Changes during
operation
No
Setting
range
0, 1
Unit of
setting
1
Default setting
0
Set Values
Value
Description
0
Less than 1,000 s: 0.1-s increments
1,000 s or over: 1-s increments
1
Less than 100 s: 0.01-s increments
100 s or over: 0.1-s increments
H
Setting the Acceleration/Deceleration Time (n019 through
n022)
·
Two acceleration times and two deceleration times can be set.
·
The acceleration time is the time required to go from 0% to 100% of the maximum fre-
quency and the deceleration time is the time required to go from 100% to 0% of the
maximum frequency. The actual acceleration or deceleration time is obtained from the
following formula.
Acceleration/Deceleration time = (Acceleration/Deceleration time set value)
´
(Frequency reference value)
¸
(Max. frequency)
Acceleration time 2 and deceleration time 2 are enabled by setting 11 for acceleration/
deceleration time selection in any of the n050 through n056 parameters for multi-func-
tion input.
Deceleration time 2 is also enabled by emergency-stop settings 19, 20, 21, and 22 in
any of the parameters for parameters n050 through n056 for multi-function input with
n005 for interruption mode selection set to 0 (i.e., deceleration stop).
Basic Operation
Chapter 5
Summary of Contents for SYSDRIVE 3G3MV A2002
Page 1: ...USER S MANUAL SYSDRIVE 3G3MV Multi function Compact Inverter Cat No I527 E2 02...
Page 15: ...Chapter 1 Overview 1 1 Function 1 2 Nomenclature 1 3 New Features 1...
Page 24: ...Chapter 2 Design 2 1 Installation 2 2 Wiring 2...
Page 89: ...Chapter 4 Test Run 4 1 Procedure for Test Run 4 2 Operation Example 4...
Page 286: ...Chapter 9 Specifications 9 1 Inverter Specifications 9 2 Option Specifications 9...
Page 311: ...Chapter 10 List of Parameters 10...
Page 342: ...Chapter 11 Using the Inverter for a Motor 11...
Page 348: ...Appendix A Standard Models...