To insert an AC reactor for surge suppression into the output side of the Inverter, set
this parameter to the motor leakage inductance added with the inductance of the AC
reactor.
·
The Inverter fully functions in vector control with the default setting for motor leakage
inductance. Therefore, set this parameter only if the motor leakage inductance is
known.
n108
Motor Leakage Inductance
Register
016C
Hex
Changes during
operation
No
Setting
range
0.000 to 655.0 (mH)
Unit of
setting
See note
1
Default setting
See
note 2
Note 1.
The value will be set in 0.01-mH increments if the inductance is less than
100 mH and 0.1-mH increments if the inductance is 100 mH or over.
Note 2.
The default setting for this parameter is the standard leakage inductance of the
maximum applicable motor.
6-1-2 Adjusting Output Torque in Vector Control
·
The Inverter controls the output torque of the motor according to the required load
torque in vector control. Normally, no special adjustments are required. Adjust the out-
put torque if the maximum torque of the motor is unavailable or improvements are
required in the output torque and response in a low-speed range.
H
Adjusting the Torque Compensation Limit (n109)
·
Adjust the set value in n109 (torque compensation limit) if the maximum torque of the
motor is insufficient or to limit the output torque to a certain degree while the motor is
driven by the Inverter in vector control.
·
Set the torque compensation limit in percentage based on the rated output current of
the Inverter as 100%.
Compensating Torque Insufficiency
·
Set n109 to a larger value if the maximum torque of the motor is insufficient.
·
Set the value in 5% increments while checking the operation of the Inverter and motor.
·
Check that no overload (OL1 or OL2) is detected. If an overload is detected, decrease
the set values or consider the use of an Inverter model or motor with a higher capacity.
Limiting Output Torque
·
Set n109 to a smaller value if the fluctuation of the output torque is large and heavy
shock is imposed on the load, or excessive output torque is not required.
·
Set the value according to the condition of the load.
Advanced Operation
Chapter 6
Summary of Contents for SYSDRIVE 3G3MV A2002
Page 1: ...USER S MANUAL SYSDRIVE 3G3MV Multi function Compact Inverter Cat No I527 E2 02...
Page 15: ...Chapter 1 Overview 1 1 Function 1 2 Nomenclature 1 3 New Features 1...
Page 24: ...Chapter 2 Design 2 1 Installation 2 2 Wiring 2...
Page 89: ...Chapter 4 Test Run 4 1 Procedure for Test Run 4 2 Operation Example 4...
Page 286: ...Chapter 9 Specifications 9 1 Inverter Specifications 9 2 Option Specifications 9...
Page 311: ...Chapter 10 List of Parameters 10...
Page 342: ...Chapter 11 Using the Inverter for a Motor 11...
Page 348: ...Appendix A Standard Models...