![background image](http://html1.mh-extra.com/html/omron/sysdrive-3g3mv-a2002/sysdrive-3g3mv-a2002_user-manual_742836304.webp)
9-19
9-2-3 DC Reactor
H
3G3HV-PUZDAB
j
The DC Reactor suppresses harmonic current
generated from the Inverter and improves the power
factor of the Inverter. The DC Reactor suppresses
harmonic current more effectively than the AC
Reactor. Furthermore, the DC Reactor can be used in
combination with the AC Reactor.
H
Applicable Models
Inverter
DC Reactor
Voltage
class
Max. applica-
ble motor ca-
pacity (kW)
Model
3G3HV-
Rated
voltage
(V)
Rated
current
(A)
Induc-
tance
(mH)
Loss
(W)
200 V
0.1 to 0.75
PUZDAB5.4A8MH 800 VDC 5.4
8
8
200 V
1.5 to 4.0
PUZDAB18A3MH
800 VDC
18
3
18
5.5 to 7.5
PUZDAB36A1MH
36
1
22
400 V
0.2 to 0.75
PUZDAB3.2A28MH 800 VDC 3.2
28
9
400 V
1.5 to 2.2
PUZDAB5.7A11MH
800 VDC
5.7
11
11
3.0 to 4.0
PUZDAB12A6.3MH
12
6.3
16
5.5 to 7.5
PUZDAB23A3.6MH
23
3.6
27
H
External Dimensions (mm)
External Dimension 1
Two, d1
mounting holes
External Dimension 2
Two, d2
mounting holes
Four, d1
mounting holes
Specifications
Chapter 9
Summary of Contents for SYSDRIVE 3G3MV A2002
Page 1: ...USER S MANUAL SYSDRIVE 3G3MV Multi function Compact Inverter Cat No I527 E2 02...
Page 15: ...Chapter 1 Overview 1 1 Function 1 2 Nomenclature 1 3 New Features 1...
Page 24: ...Chapter 2 Design 2 1 Installation 2 2 Wiring 2...
Page 89: ...Chapter 4 Test Run 4 1 Procedure for Test Run 4 2 Operation Example 4...
Page 286: ...Chapter 9 Specifications 9 1 Inverter Specifications 9 2 Option Specifications 9...
Page 311: ...Chapter 10 List of Parameters 10...
Page 342: ...Chapter 11 Using the Inverter for a Motor 11...
Page 348: ...Appendix A Standard Models...