![background image](http://html1.mh-extra.com/html/omron/sysdrive-3g3mv-a2002/sysdrive-3g3mv-a2002_user-manual_742836318.webp)
10-8
Param-
eter
No.
Ref-
er-
ence
page
Changes
during
opera-
tion
Default
setting
Unit
of
set-
ting
Set-
ting
range
Description
Name
Regis-
ter No.
n035
0123
Frequency
reference set-
ting/decimal
place selec-
tion
Set the unit of frequency reference
and frequency-related values to be
set or monitored through the Digital
Operator.
0: 0.01 Hz
1: 0.1%
2 to 39: rpm (number of motor poles)
40 to 39,899: The value to be set or
monitored at max. frequency.
Set the value as shown below.
Note
To display 50.0, for example,
set the value to 1500. The set-
ting unit of each parameter or
monitor item below varies with
the decimal place.
·
Parameters: n024 through n032 and
n120 through n127
·
Monitor Items: U-01 and U-02
jjjj
Three digits
Decimal place (See
note below)
0 to
3,999
1
0
No
5-19
n036
0124
Rated motor
current
Used to set the rated motor current
for motor overload detection (OL1)
based on the rated motor current.
Note
In vector control mode, this
parameter is used as a constant
for vector control operation.
Note
Motor overload detection (OL1)
is disabled by setting the
parameter to 0.0.
Note
The rated motor current is
default to the standard rated
current of the maximum appli-
cable motor.
0.0 to
150%
of rated
output
current
of the
Inverter
0.1 A
Varies
with the
capac-
ity
No
5-5
5-7
n037
0125
Motor protec-
tion charac-
teristics
Used to set the motor overload detec-
tion (OL1) for the electronic thermal
characteristics of the motor.
0: Protection characteristics for gen-
eral-purpose induction motors
1: Protection characteristics for
inverter-dedicated motors
2: No protection
Note
If a single Inverter is connected
to more than one motor, set the
parameter to 2 for no protection.
The parameter is also disabled
by setting n036 for rated motor
to 0.0.
0 to 2
1
0
No
6-41
List of Parameters
Chapter 10
Summary of Contents for SYSDRIVE 3G3MV A2002
Page 1: ...USER S MANUAL SYSDRIVE 3G3MV Multi function Compact Inverter Cat No I527 E2 02...
Page 15: ...Chapter 1 Overview 1 1 Function 1 2 Nomenclature 1 3 New Features 1...
Page 24: ...Chapter 2 Design 2 1 Installation 2 2 Wiring 2...
Page 89: ...Chapter 4 Test Run 4 1 Procedure for Test Run 4 2 Operation Example 4...
Page 286: ...Chapter 9 Specifications 9 1 Inverter Specifications 9 2 Option Specifications 9...
Page 311: ...Chapter 10 List of Parameters 10...
Page 342: ...Chapter 11 Using the Inverter for a Motor 11...
Page 348: ...Appendix A Standard Models...