7-27
Register No.
(Hex)
Description
Function
0039
PID input
Read based on
±
1% as
±
10 and a value
equivalent to the maximum frequency as
100%.
003A
PID output
Read based on
±
1% as
±
10 and a value
equivalent to the maximum frequency as
100%.
003B to 003C
Not used
---
003D
Communications error
Refer to the following corresponding table.
003E to 00FF
Not used
---
Note
The fault status 2, warning status, Inverter status 2, and accumulated operating time
functions are provided for 5.5kW and 7.5kW Inverters only.
D
Status Signal (Register 0020 Hex)
Bit No.
Function
0
During RUN (1: During RUN)
1
Forward/reverse operation (1: Reverse operation)
2
Inverter ready (1: Ready)
3
Fault (1: Fault)
4
Data setting error (1: Error)
5
Multi-function output 1 (1: ON)
6
Multi-function output 2 (1: ON)
7
Multi-function output 3 (1: ON)
8 to 15
Not used
D
Fault Status 1 (Register 0021 Hex)
Bit No.
Function
Bit No.
Function
0
OC
8
F
j
1
OV
9
OL1
2
OL2
10
OL3
3
OH
11
Not used
4
Not used
12
UV1
5
Not used
13
UV2
6
FBL
14
CE
7
EF
j
, STP
15
OPR
Note
When a fault results, the corresponding bit will be set to 1.
Communications
Chapter 7
Summary of Contents for SYSDRIVE 3G3MV A2002
Page 1: ...USER S MANUAL SYSDRIVE 3G3MV Multi function Compact Inverter Cat No I527 E2 02...
Page 15: ...Chapter 1 Overview 1 1 Function 1 2 Nomenclature 1 3 New Features 1...
Page 24: ...Chapter 2 Design 2 1 Installation 2 2 Wiring 2...
Page 89: ...Chapter 4 Test Run 4 1 Procedure for Test Run 4 2 Operation Example 4...
Page 286: ...Chapter 9 Specifications 9 1 Inverter Specifications 9 2 Option Specifications 9...
Page 311: ...Chapter 10 List of Parameters 10...
Page 342: ...Chapter 11 Using the Inverter for a Motor 11...
Page 348: ...Appendix A Standard Models...