4-11
H
Operation Using the Digital Operator
·
In case a fault occurs during operation, make sure the Stop Key on the Digital Operator
is easily accessible.
·
Use the Digital Operator in the same way as no-load operation.
·
First set the frequency reference to a low speed of one tenth the normal operating
speed.
H
Checking the Operating Status
·
Having checked that the operating direction is correct and that the machine is operat-
ing smoothly at slow speed, increase the frequency reference.
·
After changing the frequency reference or the rotation direction, check that there is no
vibration or abnormal sound from the motor. Check the monitor display (IOUT or multi-
function monitor U-03) to ensure that the output current is not becoming excessive.
Test Run
Chapter 4