5-38
·
For n101, set the origin search deceleration time to the time required to go from 100%
to 0% of the maximum frequency.
·
If 0 is set for the origin search deceleration time, operation will be carried out at the
default setting of 2.0 seconds.
·
For n102, set the operating level as a percentage, with the Inverter’s rated input taken
as 100%. If the Inverter’s output current drops below the level of the Inverter’s output
current, the speed search will be completed and acceleration will be resumed.
5-10-2 Multi-function digital Output
The 3G3MV incorporates three multi-function digital output terminals: one
multi-function contact outputs (MA-MC) and two multi-function photocoup-
ler outputs (P1 and P2).
Output from these terminals has a variety of functions according to the
application.
H
Selecting the Multi-function digital Output (n050 through n056)
n057
Multi-function digital Output 1
(MA/MB and MC)
Register
0139
Hex
Changes during
operation
No
Setting
range
1 to 7, 10 to 21 (see note)
Unit of
setting
1
Default setting
0
n058
Multi-function digital Output 2
(P1 and PC)
Register
013A
Hex
Changes during
operation
No
Setting
range
1 to 7, 10 to 21 (see note)
Unit of
setting
1
Default setting
1
n059
Multi-function digital Output 3
(P2 and PC)
Register
013B
Hex
Changes during
operation
No
Setting
range
1 to 7, 10 to 21 (see note)
Unit of
setting
1
Default setting
2
Note
Set values 20 and 21 are available for 5.5- and 7.5-kW Inverters only.
Set Values
Value
Function
Description
0
Fault output
ON: Fault output (with protective function working)
1
Operation in progress ON: Operation in progress (with RUN command input or
inverter output)
2
Frequency detection
ON: Frequency detection (with frequency reference
coinciding with output frequency)
Basic Operation
Chapter 5
Summary of Contents for SYSDRIVE 3G3MV A2002
Page 1: ...USER S MANUAL SYSDRIVE 3G3MV Multi function Compact Inverter Cat No I527 E2 02...
Page 15: ...Chapter 1 Overview 1 1 Function 1 2 Nomenclature 1 3 New Features 1...
Page 24: ...Chapter 2 Design 2 1 Installation 2 2 Wiring 2...
Page 89: ...Chapter 4 Test Run 4 1 Procedure for Test Run 4 2 Operation Example 4...
Page 286: ...Chapter 9 Specifications 9 1 Inverter Specifications 9 2 Option Specifications 9...
Page 311: ...Chapter 10 List of Parameters 10...
Page 342: ...Chapter 11 Using the Inverter for a Motor 11...
Page 348: ...Appendix A Standard Models...