6-33
·
The Inverter accelerates or decelerates the output frequency according to the preset
acceleration or deceleration time set in n116 (stall prevention acceleration/decelera-
tion time setting).
·
Set the parameter as percentage based on the rated Inverter current as 100%.
·
The default setting does not need any changes in normal operation.
·
Decrease the set value if the capacity of the motor is smaller than that of the Inverter or
the motor stalls with the default value.
The set value is normally 2 or 3 times higher than the rated current of the motor. Set this
current in percentage based on the rated Inverter current as 100%.
Stall Prevention during Acceleration
Output
current
n094 (Stall prevention
level during acceleration)
Time
Output
frequency
The output frequency is controlled
so that the Inverter will not stall.
Time
n115
Stall Prevention Level
Automatic Suppression
Selection
Register
0173
Hex
Changes during
operation
No
Setting
range
0, 1
Unit of
setting
1
Set Values
0
Set Values
Value
Description
0
Disabled. The set value in n094 for stall prevention during operation is
enabled in all the frequency range.
1
Enabled. The set value in n094 for stall prevention during operation is
automatically decreased when the output frequency exceeds the maximum
voltage frequency (n013).
Advanced Operation
Chapter 6
Summary of Contents for SYSDRIVE 3G3MV A2002
Page 1: ...USER S MANUAL SYSDRIVE 3G3MV Multi function Compact Inverter Cat No I527 E2 02...
Page 15: ...Chapter 1 Overview 1 1 Function 1 2 Nomenclature 1 3 New Features 1...
Page 24: ...Chapter 2 Design 2 1 Installation 2 2 Wiring 2...
Page 89: ...Chapter 4 Test Run 4 1 Procedure for Test Run 4 2 Operation Example 4...
Page 286: ...Chapter 9 Specifications 9 1 Inverter Specifications 9 2 Option Specifications 9...
Page 311: ...Chapter 10 List of Parameters 10...
Page 342: ...Chapter 11 Using the Inverter for a Motor 11...
Page 348: ...Appendix A Standard Models...