6-49
·
The stored output frequency will be cleared from the memory if n100 is set to 0. The
retained frequency is initialized if n001 for parameter initialization is set to 8 or 9.
Note
While this function is used, frequency references can only be used in remote
mode with the UP/DOWN command or inching frequency command. All multi-
step speed references are disabled.
n100
UP/DOWN Frequency
Selection
Register
0164
Hex
Changes during
operation
No
Setting
range
0, 1
Unit of
setting
1
Default setting
0
Set Values
Value
Description
0
The frequency on hold is not retained.
1
The frequency on hold for 5 s or more is retained.
Operation of UP/DOWN Function
RUN command
(Forward rotation)
UP command
(S5)
DOWN command
(S6)
Output frequency
Upper limit
Lower limit
Status
Frequency
detection
Time
Note
Status U: UP (acceleration)
D: DOWN (deceleration)
H: Hold
U1: Frequency acceleration restricted by upper limit.
D1: Frequency deceleration restricted by lower limit.
Time
Time
Time
Time
Advanced Operation
Chapter 6
Summary of Contents for SYSDRIVE 3G3MV A2002
Page 1: ...USER S MANUAL SYSDRIVE 3G3MV Multi function Compact Inverter Cat No I527 E2 02...
Page 15: ...Chapter 1 Overview 1 1 Function 1 2 Nomenclature 1 3 New Features 1...
Page 24: ...Chapter 2 Design 2 1 Installation 2 2 Wiring 2...
Page 89: ...Chapter 4 Test Run 4 1 Procedure for Test Run 4 2 Operation Example 4...
Page 286: ...Chapter 9 Specifications 9 1 Inverter Specifications 9 2 Option Specifications 9...
Page 311: ...Chapter 10 List of Parameters 10...
Page 342: ...Chapter 11 Using the Inverter for a Motor 11...
Page 348: ...Appendix A Standard Models...