2-11
2-2 Wiring
WARNING
Wiring must be performed only after confirming that the power
supply has been turned OFF. Not doing so may result in electrical
shock.
WARNING
Wiring must be performed by authorized personnel. Not doing so
may result in electrical shock or fire.
WARNING
Be sure to confirm operation only after wiring the emergency stop
circuit. Not doing so may result in injury.
WARNING
Always connect the ground terminals to a ground of 100
W
or less for
the 200-VAC class, or 10
W
or less for the 400-VAC class. Not
connecting to a proper ground may result in electrical shock.
Caution
Install external breakers and take other safety measures against
short-circuiting in external wiring. Not doing so may result in fire.
Caution
Confirm that the rated input voltage of the Inverter is the same as the
AC power supply voltage. An incorrect power supply may result in
fire, injury, or malfunction.
Caution
If you use a Braking Resistor or a Braking Resistor Unit, connect
them as specified in the manual. Not doing so may result in fire.
Caution
Be sure to wire correctly and securely. Not doing so may result in
injury or damage to the product.
Caution
Be sure to firmly tighten the screws on the terminal block. Not doing
so may result in fire, injury, or damage to the product.
Caution
Do not connect an AC power to the U, V, or W output. Doing so may
result in damage to the product or malfunction.
Design
Chapter 2
Summary of Contents for SYSDRIVE 3G3MV A2002
Page 1: ...USER S MANUAL SYSDRIVE 3G3MV Multi function Compact Inverter Cat No I527 E2 02...
Page 15: ...Chapter 1 Overview 1 1 Function 1 2 Nomenclature 1 3 New Features 1...
Page 24: ...Chapter 2 Design 2 1 Installation 2 2 Wiring 2...
Page 89: ...Chapter 4 Test Run 4 1 Procedure for Test Run 4 2 Operation Example 4...
Page 286: ...Chapter 9 Specifications 9 1 Inverter Specifications 9 2 Option Specifications 9...
Page 311: ...Chapter 10 List of Parameters 10...
Page 342: ...Chapter 11 Using the Inverter for a Motor 11...
Page 348: ...Appendix A Standard Models...