8-14
Fault
display
Probable cause and remedy
Fault name and Meaning
UL3
(flashing)
ON: Warning
UL3 (Undertorque detection)
Flashing: fault contacts do
not change state.
V/f mode: Inverter output
current fell below the preset
value in constant n118.
Vector mode: Motor current or
torque fell below the preset
value in constants n097 and
n118.
·
Load (output current or output torque) is
too low.
®
Check the driven machine and correct
the cause of the fault, or decrease the
value of constant n118 up to the
lowest value allowed for the machine.
UL3
OFF: Protective operation
ON: Output is shut OFF and
motor coasts to a stop.
When undertorque is detected,
inverter performs operation
according to the preset setting
of constant n117.
ser
(flashing)
Sequence error (SER)
A sequence change has been
input while the Inverter is in
operation.
Local or remote selection is
input while the Inverter is in
operation.
Note
The Inverter coasts to a
stop.
·
A sequence error has occurred.
®
Check and correct the sequence.
bb
(flashing)
External base block (bb)
The external base block
command has been input.
Note
The Inverter coasts to a
stop.
·
The external base block command has
been input.
®
Remove the cause of external base
block input.
·
The sequence is incorrect.
®
Check and change the external fault
input sequence including the input
timing and NO or NC contact.
Maintenance Operations
Chapter 8
Summary of Contents for SYSDRIVE 3G3MV A2002
Page 1: ...USER S MANUAL SYSDRIVE 3G3MV Multi function Compact Inverter Cat No I527 E2 02...
Page 15: ...Chapter 1 Overview 1 1 Function 1 2 Nomenclature 1 3 New Features 1...
Page 24: ...Chapter 2 Design 2 1 Installation 2 2 Wiring 2...
Page 89: ...Chapter 4 Test Run 4 1 Procedure for Test Run 4 2 Operation Example 4...
Page 286: ...Chapter 9 Specifications 9 1 Inverter Specifications 9 2 Option Specifications 9...
Page 311: ...Chapter 10 List of Parameters 10...
Page 342: ...Chapter 11 Using the Inverter for a Motor 11...
Page 348: ...Appendix A Standard Models...