6-42
n038
Motor Protection Time
Register
0126
Hex
Changes during
operation
No
Setting
range
1 to 60 (min)
Unit of
setting
1 min
Default setting
8
Set Values
·
This parameter is used to set the electronic thermal protection constant of motor over-
load detection OL1.
·
The default setting does not need any changes in normal operation.
·
To set the parameter according to the characteristics of the motor, confirm the thermal
time constant with the motor manufacturer and set the parameter with some margin. In
other words, set the value a little shorter than the thermal time constant.
·
To detect motor overloading more quickly, reduce the set value, provided that it does
not cause any application problems.
6-10-3 Cooling Fan Operation Function (n039)
·
This parameter is used to operate the cooling fan of the Inverter while the Inverter is
turned ON or only while the Inverter is in operation.
n039
Cooling Fan Operation
Register
0127
Hex
Changes during
operation
No
Setting
range
0, 1
Unit of
setting
1
Default setting
0
Set Values
Value
Description
0
The fan rotates only while the RUN command is input and for 1 minute after
the Inverter stops operating.
1
The fan rotates while the Inverter is turned ON.
·
This parameter is available only if the Inverter incorporates a cooling fan.
·
If the operation frequency of the Inverter is low, the life of the fan can be prolonged by
setting the parameter to 0.
6-10-4 Momentary Power Interruption Compensation
(n081)
·
The parameter specifies the processing that will be performed when a momentary
power interruption occurs.
Advanced Operation
Chapter 6
Summary of Contents for SYSDRIVE 3G3MV A2002
Page 1: ...USER S MANUAL SYSDRIVE 3G3MV Multi function Compact Inverter Cat No I527 E2 02...
Page 15: ...Chapter 1 Overview 1 1 Function 1 2 Nomenclature 1 3 New Features 1...
Page 24: ...Chapter 2 Design 2 1 Installation 2 2 Wiring 2...
Page 89: ...Chapter 4 Test Run 4 1 Procedure for Test Run 4 2 Operation Example 4...
Page 286: ...Chapter 9 Specifications 9 1 Inverter Specifications 9 2 Option Specifications 9...
Page 311: ...Chapter 10 List of Parameters 10...
Page 342: ...Chapter 11 Using the Inverter for a Motor 11...
Page 348: ...Appendix A Standard Models...