2-21
D
Example of 3-wire Sequence Connections
Stop
switch
(NC)
RUN
switch
(NO)
Direction switch
RUN input (Operates with the RUN switch closed)
Stop input (Stops with the stop switch opened)
Sequence input common
Sequence input common
Note
Set parameter 052 to forward/reverse rotation command 0 for 3-wire sequence
input.
2-2-3 Wiring around the Main Circuit
H
Wire Size, Terminal Screw, Screw Tightening Torque, and
Molded-case Circuit Breaker Capacities
·
For the main circuit and ground, always use 600-V polyvinyl chloride
(PVC) cables.
·
If any cable is long and may cause voltage drops, increase the wire size according to
the cable length.
D
3-phase 200-VAC Model
Model
3G3MV-
Terminal symbol
Termi-
nal
screw
Screw
tighten-
ing
torque
(N
S
m)
Wire
size
(mm
2
)
Recom-
mended
wire
size
(mm
2
)
Molded-
case
circuit
breaker
capac-
ity (A)
A2001
R/L1, S/L2, T/L3, B1, B2,
--, +1, +2, U/T1, V/T2,
W/T3
M3.5
0.8 to 1.0 0.75 to 2 2
5
A2002
R/L1, S/L2, T/L3, B1, B2,
--, +1, +2, U/T1, V/T2,
W/T3
M3.5
0.8 to 1.0 0.75 to 2 2
5
A2004
R/L1, S/L2, T/L3, B1, B2,
--, +1, +2, U/T1, V/T2,
W/T3
M3.5
0.8 to 1.0 0.75 to 2 2
5
Design
Chapter 2
Summary of Contents for SYSDRIVE 3G3MV A2002
Page 1: ...USER S MANUAL SYSDRIVE 3G3MV Multi function Compact Inverter Cat No I527 E2 02...
Page 15: ...Chapter 1 Overview 1 1 Function 1 2 Nomenclature 1 3 New Features 1...
Page 24: ...Chapter 2 Design 2 1 Installation 2 2 Wiring 2...
Page 89: ...Chapter 4 Test Run 4 1 Procedure for Test Run 4 2 Operation Example 4...
Page 286: ...Chapter 9 Specifications 9 1 Inverter Specifications 9 2 Option Specifications 9...
Page 311: ...Chapter 10 List of Parameters 10...
Page 342: ...Chapter 11 Using the Inverter for a Motor 11...
Page 348: ...Appendix A Standard Models...