5-10
5-4 Setting the Local/Remote Mode
The 3G3MV operates in local or remote mode. The following description
provides information on these modes and how to select them.
H
Basic Concept
Operation mode
Basic concept
Description
Local
The Inverter in a system
operates independently in
this mode so that the
Inverter can be checked
independently.
Operation Command
Starts with the RUN Key of the Digital
Operator and stops with the
STOP/RESET Key.
Frequency Reference
Set with the Digital Operator or the FREQ
adjuster.
Set with frequency reference selection in
local mode in n007.
Remote
The Inverter in a system
operates according to the
control signal of the host
controller.
Operation Command
Selectable from four types and set in
n003.
Frequency Reference
Selectable from ten types and set in
n004.
H
Local/Remote Selection Methods
·
The following two selection methods are available to set the Inverter to local or remote
mode. However, it is not possible to switch between local and remote modes during
operation command input.
S
Select the mode with the LO/RE Key of the Digital Operator.
S
Set any one of multi-function inputs 1 through 7 (n050 through n056) to 17 to set the
Inverter to local mode with control input turned ON.
Note
If the above setting is made, mode selection will be possible only with multi--func-
tion input, and not with the Digital Operator.
·
The inverter always goes into remote mode when the power is turned ON. To operate
immediately after power--up, preset the RUN command and frequency reference set-
tings in remote mode.
Basic Operation
Chapter 5
Summary of Contents for SYSDRIVE 3G3MV A2002
Page 1: ...USER S MANUAL SYSDRIVE 3G3MV Multi function Compact Inverter Cat No I527 E2 02...
Page 15: ...Chapter 1 Overview 1 1 Function 1 2 Nomenclature 1 3 New Features 1...
Page 24: ...Chapter 2 Design 2 1 Installation 2 2 Wiring 2...
Page 89: ...Chapter 4 Test Run 4 1 Procedure for Test Run 4 2 Operation Example 4...
Page 286: ...Chapter 9 Specifications 9 1 Inverter Specifications 9 2 Option Specifications 9...
Page 311: ...Chapter 10 List of Parameters 10...
Page 342: ...Chapter 11 Using the Inverter for a Motor 11...
Page 348: ...Appendix A Standard Models...