5-8
n012
Maximum Voltage (VMAX)
Register
010C
Hex
Changes during
operation
No
Setting
range
0.1 to 255.0 [0.1 to 510.0] (V)
Unit of
setting
0.1 V
Default setting
200.0
[400.0]
n013
Maximum Voltage Frequency
(FA)
Register
010D
Hex
Changes during
operation
No
Setting
range
0.2 to 400.0 (Hz)
Unit of
setting
0.1
Hz
Default setting
60.0
n014
Middle Output Frequency (FB)
Register
010E
Hex
Changes during
operation
No
Setting
range
0.1 to 399.9 (Hz)
Unit of
setting
0.1
Hz
Default setting
1.5
n015
Middle Output Frequency
Voltage (VC)
Register
010F
Hex
Changes during
operation
No
Setting
range
0.1 to 255.0 [0.1 to 510.0] (V)
Unit of
setting
0.1 V
Default setting
12.0
[24.0]
(seenote2)
n016
Minimum Output Frequency
(FMIN)
Register
0110
Hex
Changes during
operation
No
Setting
range
0.1 to 10.0 (Hz)
Unit of
setting
0.1
Hz
Default setting
1.5
n017
Minimum Output Frequency
Voltage (VMIN)
Register
0111
Hex
Changes during
operation
No
Setting
range
0.1 to 50.0 [0.1 to 100.0] (V)
Unit of
setting
0.1 V
Default setting
12.0
[24.0]
(seenote2)
Note 1.
[ ] values indicate those for 400-V-class Inverters.
Note 2.
For 5.5- and 7.5-kW Inverters, this value is set to 10.0 V for 200-V-class models
and to 20.0 V for 400-V-class models.
Output
voltage (V)
Note 1.
Set the parameters so that
the following condition will be
satisfied.
n016
n014 < n013
n011
Note 2.
The value set in n015 will be
ignored if parameters n016
and n014 are the same in
value.
Frequency (Hz)
n012 (VMAX)
n015 (VC)
n017 (VMIN)
n016
(FMIN)
n014
(FB)
n013
(FA)
n011
(FMAX)
Basic Operation
Chapter 5
Summary of Contents for SYSDRIVE 3G3MV A2002
Page 1: ...USER S MANUAL SYSDRIVE 3G3MV Multi function Compact Inverter Cat No I527 E2 02...
Page 15: ...Chapter 1 Overview 1 1 Function 1 2 Nomenclature 1 3 New Features 1...
Page 24: ...Chapter 2 Design 2 1 Installation 2 2 Wiring 2...
Page 89: ...Chapter 4 Test Run 4 1 Procedure for Test Run 4 2 Operation Example 4...
Page 286: ...Chapter 9 Specifications 9 1 Inverter Specifications 9 2 Option Specifications 9...
Page 311: ...Chapter 10 List of Parameters 10...
Page 342: ...Chapter 11 Using the Inverter for a Motor 11...
Page 348: ...Appendix A Standard Models...