7-16
7-3-2 Data Write/Broadcast Data Write (Function Code: 10 Hex)
H
Settings and Response
·
To write data to the Inverter, such as control I/O and parameter set value data, issue the
following DSR message.
·
Consecutive data of a maximum of 16 words (32 bytes for 16 registers) can be written
per DSR message.
·
The register number is allocated to each function item, such as control I/O and param-
eter functions. The register number of each parameter is indicated wherever the
parameter is explained in this manual and in
Section 10 List of Parameters
. For regis-
ter numbers other than those of parameters, refer to
7-6 Register Number Allocations
in Details
.
D
DSR Message
Byte No.
Data
1
Slave address
2
Function code (10 Hex)
3
Register No. of write start data
4
Register No. of write start data
5
No. of registers of write data (max. 16)
6
No. of registers of write data (max. 16)
7
Data of start register
8
Data of next register
MSB
9
Data of next register
LSB
10
Data of next register
MSB
11
Data of next register
LSB
12
Data of next register
MSB
13
Data of next register
LSB
:
:
:
n--1
CRC-16 check
n
CRC-16 check
Communications
Chapter 7
Summary of Contents for SYSDRIVE 3G3MV A2002
Page 1: ...USER S MANUAL SYSDRIVE 3G3MV Multi function Compact Inverter Cat No I527 E2 02...
Page 15: ...Chapter 1 Overview 1 1 Function 1 2 Nomenclature 1 3 New Features 1...
Page 24: ...Chapter 2 Design 2 1 Installation 2 2 Wiring 2...
Page 89: ...Chapter 4 Test Run 4 1 Procedure for Test Run 4 2 Operation Example 4...
Page 286: ...Chapter 9 Specifications 9 1 Inverter Specifications 9 2 Option Specifications 9...
Page 311: ...Chapter 10 List of Parameters 10...
Page 342: ...Chapter 11 Using the Inverter for a Motor 11...
Page 348: ...Appendix A Standard Models...