6-46
Set Values
·
Select the operation status to be accumulated
.
Value
Description
0
Accumulate the Inverter’s power-ON time (the time from when the power is
turned ON until it is shut OFF).
1
Accumulate the Inverter’s RUN time (the time that the RUN command is
being input).
n088
Accumulated Operating
Time Selection
Register
0158
Hex
Changes during
operation
No
Setting
range
0 to 6,550
Unit of
setting
10 H
Default setting
0
·
Set the initial value for the accumulated operating time with 10 hours set as 1. The ac-
cumulation will begin from the time that is set.
Note
To clear (i.e., set to 0) the monitor value (U--13) for the accumulated operating time,
set n088 to 0. The monitor value cannot be cleared by setting n001 (parameter
write-prohibit selection/parameter initialization) to 8 or 9 (initialize).
6-10-8 Frequency Detection Function
·
The 3G3MV has the following frequency detection functions.
Frequency Detection:
Detects that the frequency reference coincides with the output frequency.
Frequency Detection Levels 1 and 2:
Detects that the output frequency is the same as or higher or lower than the set value
(frequency detection level) in n095.
·
The multi-function outputs (n057 to n059) must be set for the frequency detection func-
tion.
Advanced Operation
Chapter 6
Summary of Contents for SYSDRIVE 3G3MV A2002
Page 1: ...USER S MANUAL SYSDRIVE 3G3MV Multi function Compact Inverter Cat No I527 E2 02...
Page 15: ...Chapter 1 Overview 1 1 Function 1 2 Nomenclature 1 3 New Features 1...
Page 24: ...Chapter 2 Design 2 1 Installation 2 2 Wiring 2...
Page 89: ...Chapter 4 Test Run 4 1 Procedure for Test Run 4 2 Operation Example 4...
Page 286: ...Chapter 9 Specifications 9 1 Inverter Specifications 9 2 Option Specifications 9...
Page 311: ...Chapter 10 List of Parameters 10...
Page 342: ...Chapter 11 Using the Inverter for a Motor 11...
Page 348: ...Appendix A Standard Models...