5-25
5-6-5 Setting Frequency References by Pulse Train
Input
By setting n004 for frequency reference selection to 5 for enabling the
pulse train reference control terminal, frequency references can be
executed by pulse train input through the PR terminal.
The following description provides information on the n149 parameter
(pulse train input scale), which is used to execute frequency references by
pulse train input.
H
Setting the Pulse Train Input Scale (n149)
·
Set this parameter to the pulse train input scale so that frequency references can be
executed by pulse train input.
·
Set the maximum pulse train frequency in 10-Hz increments based on 10 Hz as 1. A
proportional relationship is applied to frequencies less than the maximum frequency.
n149
Pulse Train Input Scale
Register
0195
Hex
Changes during
operation
No
Setting
range
100 to 3,300
Unit of
setting
1 (10 Hz)
Default setting
2,500
Note 1.
For example, to set the maximum frequency reference with pulse train fre-
quency input at 10 kHz, set the parameter to 1000 from the following formula.
10,000 (Hz)/10 (Hz) = 1,000
Note 2.
Input the pulse train into the frequency reference common (FC) and pulse train
input (RP) terminals under the following conditions.
High level: 3.5 to 13.2 V
Low level: 0.8 V max.
The response frequency is within a range from 0 to 33 kHz (30% to 70% ED).
ED = Operating Duty Cycle.
H
Setting the Pulse Train Frequency Reference Gain/Bias
(n074/n075)
·
Set the input characteristics of pulse train input.
·
Gain: Set the gain in percentage based on the maximum frequency of the pulse train
input scale in n149 as 100%.
·
Bias: Set the bias in percentage for frequency reference input at 0-Hz pulse train input
based oh the maximum frequency as 100%.
Basic Operation
Chapter 5
Summary of Contents for SYSDRIVE 3G3MV A2002
Page 1: ...USER S MANUAL SYSDRIVE 3G3MV Multi function Compact Inverter Cat No I527 E2 02...
Page 15: ...Chapter 1 Overview 1 1 Function 1 2 Nomenclature 1 3 New Features 1...
Page 24: ...Chapter 2 Design 2 1 Installation 2 2 Wiring 2...
Page 89: ...Chapter 4 Test Run 4 1 Procedure for Test Run 4 2 Operation Example 4...
Page 286: ...Chapter 9 Specifications 9 1 Inverter Specifications 9 2 Option Specifications 9...
Page 311: ...Chapter 10 List of Parameters 10...
Page 342: ...Chapter 11 Using the Inverter for a Motor 11...
Page 348: ...Appendix A Standard Models...