4-7
3
Initializing Parameters
·
Initialize the parameters using the following procedure.
·
To initialize the parameters, set n01 to 8.
Key sequence
Indicator
Display
example
Explanation
Power On
Press the Mode Key repeatedly until the
PRGM indicator is lit.
Press the Enter Key. The data of n001 will be
displayed.
Use the Increment or Decrement Key to set
n01 to 8. The display will flash.
Press the Enter Key so that the set value will
be entered and the data display will be lit.
---
Parameter n001 will be initialized and reset to
1 from 8.
In approximately
1 s.
The parameter number will be displayed.
Test Run
Chapter 4