Data sheet 12/20-EM083-11

Emergency lighting units

EM powerLED

 

Product description

•  Fixed output LED Driver for mains operation

•  Emergency lighting LED Driver with manual test function

•  For self-contained emergency lighting

•  For LED modules with a forward voltage of 50 – 220 V

•  For luminaire installation

•  Low profile casing (21 x 30 mm)

•  5 years guarantee

Properties

•  6 – 75 W output power

•  Constant current LED operation

•  Adjustable output current between 80 and 400 mA via ready-

2mains Programmer or I-SELECT 2 plugs

•  Integrated emergency lighting unit

•  1 or 3 hr rated duration

•  Automatic shutdown of output if LED load is out of range

•  Green charge status display LED

•  Electronic multi-level charge system

•  Polarity reversal protection for battery

•  Deep discharge protection

•  Short-circuit-proof battery connection

Batteries

•  High-temperature cells

•  NiCd or NiMH batteries

•  D, Cs or LA cells

•  4-year design life

•  1-year guarantee

•  For battery compatibility refer to table „Battery selection“

È

Standards

, page 6

Wiring diagrams and installation examples

, page 6 

EM powerLED BASIC FX lp 75 W

Combined emergency lighting LED Driver

 

Summary of Contents for 89800598

Page 1: ...tion Adjustable output current between 80 and 400 mA via ready 2mains Programmer or I SELECT 2 plugs Integrated emergency lighting unit 1 or 3 hr rated duration Automatic shutdown of output if LED load is out of range Green charge status display LED Electronic multi level charge system Polarity reversal protection for battery Deep discharge protection Short circuit proof battery connection Batteri...

Page 2: ... load 50 ms Max output current peak non repetitive output current 35 Output LF current ripple 120 Hz 5 Output current tolerance 5 Ambient temperature ta6 5 50 C Max casing temperature tc 75 C Mains surge capability between L N 1 kV Mains surge capability between L N PE 2 kV Surge voltage at output side against PE 2 kV Dimensions LxBxH 360 x 30 x 21 mm Mains voltage changeover threshold according t...

Page 3: ... mA 0 95 25 00 kΩ 250 mA 50 V 220 V 55 W 60 W 270 mA 0 97 20 00 kΩ 300 mA 50 V 220 V 66 W 71 W 320 mA 0 97 16 67 kΩ 350 mA 50 V 214 V 75 W 82 W 360 mA 0 98 14 29 kΩ 400 mA 50 V 188 V 75 W 82 W 370 mA 0 98 short circuit 0 Ω Emergency operation EM powerLED BASIC FX 213 233 lp 75W 220V 3 see page 8 50 V 220 V 2 5 W all EM powerLED BASIC FX 214 234 lp 75W 220V 4 see page 8 50 V 220 V 3 5 W all EM powe...

Page 4: ... ACCES SORIES Ordering data Type Article number Packaging bag Packaging carton Weight per pc LED EM green 89899605 25 pc s 200 pc s 0 011 kg LED EM green ultra high brightness 89899756 25 pc s 200 pc s 0 012 kg Product description For connection to the emergency lighting LED Driver For checking the device function Test switch EM2 ACCES SORIES Ordering data Type Article number Packaging bag Packagi...

Page 5: ... mA 16 67 kΩ 10 pc s 0 001 kg I SELECT 2 PLUG 325MA BL 28001109 Blue 0325 mA 325 mA 15 38 kΩ 10 pc s 0 001 kg I SELECT 2 PLUG 350MA BL 28001110 Blue 0350 mA 350 mA 14 29 kΩ 10 pc s 0 001 kg I SELECT 2 PLUG 375MA BL 28001111 Blue 0375 mA 375 mA 13 33 kΩ 10 pc s 0 001 kg I SELECT 2 PLUG 400MA BL 28001112 Blue 0400 mA 400 mA 12 50 kΩ 10 pc s 0 001 kg I SELECT 2 PLUG MAX BL 28001099 Blue MAX MAX 0 00 ...

Page 6: ...s is not allowed and may cause damage to the LEDs The hot plug in of LEDs during normal operation may result in high current peaks EM powerLED BASIC N L S L I sel 2 1 I sel 2 2 LED Battery Test switch 220 240 V L N 50 60 Hz Orange Pink Indication LED 3 Installation Wiring 3 1 Wiring diagrams The EM powerLED is designed for a life time stated above under reference conditions and with a failure prob...

Page 7: ...ood practice in the wiring layout Within the luminaire the switched and unswitched 50Hz supply wiring must be routed as short as possible and be kept as far away as possible from the LED leads Through wiring may affect the emc performance of the luminaire The length of LED leads must not be exceeded The output current depends on the forward voltage and the tolerance of the LED modules 4 Mechanical...

Page 8: ...8 6 9 12 14 25 8 A 280 μs 5 1 Maximum loading of automatic circuit breakers Calculation uses typical values from ABB series S200 as a reference Actual values may differ due to used circuit breaker types and installation environment Insulate the battery LED test switch and indicator LED in the luminaire according to the U OUT rating of the LED Driver 5 2 Insulation matrix Mains Switched Live Batter...

Page 9: ...ery voltage 850 960 mA battery discharge current tolerance EM powerLED BASIC FX 214 234 lp 75W 220V Article number 89800599 89800602 4 8 V battery voltage 850 960 mA battery discharge current tolerance LED current mA VLED V VLED V LED current mA 50 90 70 110 150 210 130 170 190 10 20 30 0 70 60 40 50 80 50 90 70 110 150 210 130 170 190 10 20 30 0 50 40 60 EM powerLED BASIC FX 215 235 lp 75W 220V A...

Page 10: ... Output voltage V 0 4 0 5 0 6 0 7 0 8 0 9 1 0 20 50 60 70 80 90 30 40 100 Load Power factor 100 load corresponds to the max output power full load according to the table on page 2 100 mA 400 mA 250 mA 5 7 THD vs load THD without harmonic 5 mA or 0 6 of the input current 5 5 Efficiency vs load 5 6 Power factor vs load 5 4 Operating window Operating window 100 Make sure that the LED Driver is operat...

Page 11: ... be activated again The restart can either be done via mains reset or via interface ready2mains 7 3 No load operation The EM powerLED will not be damaged in no load operation The output will be deactivated and is therefore free of voltage If a LED load is connected the device has to be restarted before the output will be activated again 7 4 Overload protection If the output voltage range is exceed...

Page 12: ...ON 89800389 remote box 1 x 4 Pack NiCd 4D CON 89800390 remote box 1 x 5 Pack NiCd 5D CON 28001181 NiMH 2 2Ah Cs cells stick 1 x 3 Accu NiMH 3A 28002088 stick 1 x 4 Accu NiMH 4A 28002089 stick 1 x 5 Accu NiMH 5A 28002090 side by side 5 x 1 Accu NiMH 5B 28002093 remote box 1 x 3 Pack NiMH 2 2Ah 3 CON 28001898 remote box 1 x 4 Pack NiMH 2 2Ah 4 CON 28001899 NiMH 4Ah LA cells stick 1 x 3 Accu NiMH 4Ah...

Page 13: ...harge cycles 4 cycles per year plus 30 cycles during comissioning Max storage time 12 months 4 0 Ah International designation HRMU 19 90 Battery voltage cell 1 2 V Cell type LA Case temperature range to ensure 4 years design life 5 C to 45 C Max short term temperature reduced life time 70 C Max number discharge cycles 4 cycles per year plus 30 cycles during comissioning Max storage time 12 months ...

Page 14: ...ith 500VDC for one second This test voltage should be connected between the interconnected phase and neutral terminals and the earth terminal The insulation resistance must be at least 2MΩ As an alternative IEC 60598 1 Annex Q describes a test of the electrical strength with 1500VAC or 1 414 x 1500VDC To avoid damage to the electronic devices this test must not be conducted 9 3 Conditions of use a...