background image

Fcontrol Basic

FSDM2.5..50M

Frequency inverter with integrated sine 

lter for 3 ~ fans

Operating Instructions

Speed controller with 0...10 V input for presetting the fan speed

Keep for reference!

L-BAL-E162-GB 2022/02 Index 008

Part.-No. 

english

Summary of Contents for Fcontrol Basic FSDM Series

Page 1: ...M2 5 50M Frequency inverter with integrated sine filter for 3 fans Operating Instructions Speed controller with 0 10 V input for presetting the fan speed Keep for reference L BAL E162 GB 2022 02 Index 008 Part No english ...

Page 2: ...nlet 11 4 5 Outdoor installation 12 4 6 Installation location for agriculture 12 4 7 Temperature influences during commissioning 12 5 Electrical installation 12 5 1 Safety precautions 12 5 2 Terminal compartment 13 5 3 EMC compatible installation 14 5 3 1 Motor cable 14 5 3 2 Control cables 14 5 3 3 Harmonics current for devices 16 A 14 5 3 4 Harmonics current and line impedance for devices 16 A an...

Page 3: ...20 5 15 Potential at control voltage connections 21 5 16 Option add on modules 21 6 Commissioning 22 6 1 Prerequisites for commissioning 22 7 Diagnostics Faults 22 8 Enclosure 24 8 1 Technical data 24 8 1 1 Max load dependent on ambient temperature and line voltage 26 8 2 Connection diagram 27 8 3 Dimensions mm 28 8 4 Manufacturer reference 30 8 5 Service note 30 Operating Instructions Fcontrol Ba...

Page 4: ...lity Concurrence between the contents of these operating instructions and the described hardware and software in the device has been examined It is still possible that non compliances exist no guarantee is assumed for complete conformity To allow for future developments construction methods and technical data given are subject to alteration We do not accept any liability for possible errors or omi...

Page 5: ...he instructions of AEL DLG VdS 2 4 Requirements placed on the personnel due diligence Persons entrusted with the planning installation commissioning and maintenance and servicing in connection with the frequency inverter must have the corresponding qualifications and skills for these jobs In addition they must be knowledgeable about the safety regulations directives rules for the prevention of acci...

Page 6: ...he device Attention Automatically restart after a power failure or mains disconnection 2 7 Modifications interventions in the device Attention For reasons of safety no unauthorized interventions or modifications may be made on the device All planned modifications must be authorized by the manufacturer in writing Use only genuine spare parts genuine wearing parts genuine accessories from ZIEHL ABEGG T...

Page 7: ... description The frequency inverters generate their 3 output with variable voltage and frequency from the three phase mains on the input The devices are constructed in accordance with the general requirement in EN 61800 2 for adjustable speed electrical power systems and is intended for one quadrantdrives The output frequency is set by an external signal 0 10 V 0 20 mA PWM 3 3 Rating plate The nam...

Page 8: ...or women the fan should be lifted out by two persons according to REFA The values may differ from country to country Wear safety shoes and gloves for handling Assemble the device on a clean and stable base Do not distort during assembly Use the appropriate mounting devices for proper installation of the unit A mounting on vibrating base is not permissible if no data to the vibration strength is mad...

Page 9: ...gly larger clearance or thermal shielding is required 4 3 Fastening the device The type of fastening and the number of fastening points are dependent on the housing design All the fastening points available must be used for safe fastening Proceed as follows Type FSDM2 5M Fastening at 3 points GM00006A_M 15 12 2015 3 2 1 Drill fastening point 1 Screw in flat head screw up to a distance of approx 2 m...

Page 10: ... points GM00002A_M 15 12 2015 1 7 2 3 4 5 6 8 Drill 8 fastening points Screw in fastening point screws 1 4 up to a distance of approx 5 mm and mount the device Tighten fastening point screws 1 4 Screw in fastening point screws 5 8 and tighten Operating Instructions Fcontrol Basic model series FSDM2 5 50M Mounting L BAL E162 GB 2022 02 Index 008 Part No 10 30 ...

Page 11: ... plate 1 Cable inlet with step nozzles factory installed 1A 3 x max 18 mm 1B 3 x max 14 mm 1C 3 x max 11 mm 1D 4 8 x max 8 mm 2 attached cable inlet for cable glands 2A 17 21 mm 2B 12 5 17 mm 3 Fastening screws Sheet metal housing 1 Inlet mains connection 40 mm 2 Inlet motor connection 40 mm 3 Inlet control cables 20 mm Information Cable glands can be used alternatively not included in delivery Th...

Page 12: ...lways be present when working on energized parts or lines who disconnects in case of emergency Electrical equipment must be checked regularly Loose connections are to be re tightened and damaged cables must be replaced immediately Always keep switch cabinets and all electrical supply facilities locked Access is only allowed for authorized persons using a key or special tool Operating the device wi...

Page 13: ... mm2 2 5 mm2 F S DM8 A M 4 mm2 2 5 mm2 4 mm2 2 5 mm2 F S DM10 A M 4 mm2 2 5 mm2 4 mm2 2 5 mm2 F S DM16 A M 4 mm2 2 5 mm2 4 mm2 2 5 mm2 F S DM22 A M 6 mm2 6 mm2 6 mm2 6 mm2 F S DM32 A M 16 mm2 10 mm2 10 mm2 6 mm2 F S DM40 A M 25 mm2 16 mm2 16 mm2 10 mm2 F S DM50 A M 25 mm2 16 mm2 16 mm2 10 mm2 Possible cross sections of terminals for control section For all types rigid flexible Brake control 0 25 1 ...

Page 14: ...sary that the equipment is connected only to a supply with a short circuit power SSC greater than or equal to RSCE x Sequ SSC Short circuit power from line at the interface point between the user s supply and the public system Sequ Rated apparent power for three phase devices Sequ 3 x UI x Iequ UI phase to phase voltage se Technical data Line voltage Iequ rated current of the device se Technical d...

Page 15: ...current operated protective devices may not be used To ensure as high a degree of reliability as possible we recommend a tripping current of 300 mA Residual current circuit breaker type B 5 6 Inverter output 5 6 1 Motor connection The motor leads are connected to the terminals PE U V W Several fans can be connected to the controller the maximum total current of all motors must not exceed the curre...

Page 16: ...tor with thermistors TP the jumper J1 must be plugged at the top A maximum of six individual thermistors DIN 44081 or DIN 44082 may be connected in series to a single device J1 TP Motor with thermostats TB For motor with thermostats TB jumper plugged at bottom factory setting J1 TB When a connected thermostat or thermistor responds interruption between the two terminals TB TP the device switches o...

Page 17: ...es FSDM2 5 16 0 10 V factory setting Control via external setting signal 0 10 V or Speed setting by external potenziometer 10 kΩ at terminals 10 V and GND pick of off at terminal E1 E1 D1 GND 0 10 V Analog In 1 E1 1 E1 2 V E1 D1 GND 10V Analog In 1 10 V DC Out 10 kΩ 30 08 11 i_jumper_if_basic_0_10v eps 0 20 mA Control via external setting signal 0 20 mA E1 D1 GND 0 20 mA Analog In 1 E1 1 E1 2 mA 31...

Page 18: ... DC Out 24 V 15 28 V GND E1 E1 1 PWM 10 V E1 D1 GND 10V Analog In 1 10 V DC Out 24V 24 V DC Out PWM f 1 10 kHz 10 kΩ 0 20 mA Control via external setting signal 0 20 mA E1 D1 GND 0 20 mA Analog In 1 E1 1 mA 13 06 2014 i_jumper_motor_mounted_0_20ma eps 5 9 Output voltage 10 V Voltage supply e g for speed setting by external potentiometer Connection 10 V GND max load see Technical data und connectio...

Page 19: ... outputs K1 An external fault indicator is available over the potential free contact of the built in relays max contact rating Technical data and connection diagram Function factory setting for K1 For operation the relay is energized connections 13 and 14 are bridged For fault the relay is de energized Diagnostics faults When switching off via enable D1 Digital In 1 the relay remains energized 5 13...

Page 20: ...0 V 50 60 Hz L1 L2 U V TB TB W N N 1 17 5 13 18 Auto 0 100 S D 4 10 2 6 14 7 11 Regelgerät controller L3 19 N N M 3 U V W PE TB Y Δ q 3 Motor mit eingebauten Thermostatschaltern with internal thermostats TB L3 16 Switch position 0 Switch OFF supply line lockable AUTO Operation Control 100 Operation Bypass controller without supply Technical data Line voltage max 690 V 50 60 Hz Rated current Type S...

Page 21: ...nto a MODBUS network The members can be addressed automatically by an additional connection The device can be communicated with using the hand held terminal type A G 247NW Connection by cable via the MODBUS interface or wirelessly by radio AM MODBUS W On the AM MODBUS WB this can be done wirelessly using Bluetooth and the ZAset mobile app AM PREMIUM AM PREMIUM W 349046 349051 Universal control mod...

Page 22: ...OFF and automatically ON when the voltage has been re stored Check line voltage and pre fusing ON energized 13 14 bridged Normal operation without fault 1 energized 13 14 bridged No enable OFF Terminals D1 24 V Digital In 1 not bridged Switch off by external contact ena ble device ON OFF 2 energized 13 14 bridged Temperature management active The device has an active temperature management to prote...

Page 23: ...oltage Intermediate circuit voltage above fixed limit for longer than 75s Reason for excessively high line voltage or alternator motor operation The modulation is switched off immedi ately at overvoltage error message after 75 s Automatic switching back on and switch ing off of error message when the volt age drops below the fixed limit for at least 15 s Check line voltage Prevent generator motor oper...

Page 24: ...emperature in controller Check cooling of the controller 17 de energized 13 14 interrupted Overload fault The controller was switched off by the current limitation The error is set after detecting 4 times I2 t process maximum overload applied for 60 s After every detection IGTB Recovery Flag is set there is a 30 s wait until a new attempt is started The respective errors must alway have a shorter i...

Page 25: ...x 10 mA short circuit proof Max contact rating of the relay 2 A 250 V AC Max permissible ambient tempera ture 55 C Min permissible ambient tempera ture 0 C if mains voltage is not switched off up to 20 C To avoid condensation the device must be continuously energized due to the application of heat with interruptions such that cooling to the point of condensation does not occur Permissible temperatu...

Page 26: ...e rated temperature following table The average value measured during a 24 h period must be 5 K under the max ambient temperature For installation in a switch cabinet the device s dissipation and its possible affect on the ambient temperature must be taken into consideration Since the power loss in the device increases with rising line voltage the following table must be observed Maximal load depen...

Page 27: ...V AC 8 2 1 Connection suggestion for several motors with motor protection units type S DT Full motor protection by switch off when activating the attached thermostat switches TB Reset after malfunction by key press Line protection A thermal over current sensor and a magnetic short circuit releasing elements are the parts of the integral line protection Adjustment to the thermal overcurrent sensor t...

Page 28: ...8 3 Dimensions mm FSDM2 5M FSDM5 8 10 16M FSDM22M Operating Instructions Fcontrol Basic model series FSDM2 5 50M Enclosure L BAL E162 GB 2022 02 Index 008 Part No 28 30 ...

Page 29: ...FSDM32 40 50M Operating Instructions Fcontrol Basic model series FSDM2 5 50M Enclosure L BAL E162 GB 2022 02 Index 008 Part No 29 30 ...

Page 30: ... http www ziehl abegg com 8 5 Service note If you have any technical questions while commissioning or regarding malfunctions please contact our technical support for control systems ventilation technology phone 49 0 7940 16 800 Email fan controls service ziehl abegg de Our worldwide contacts are available in our subsidiaries for deliveries outside of Germany see www ziehl abegg com Operating Instr...