189
Interrupt Functions
Section 5-1
Input Terminal Arrangement
Setting the Input Functions in the PLC Setup
Normally, bits CIO 0.00 to CIO 0.03 and CIO 1.00 to CIO 1.03 are used as
normal inputs. When using these inputs for input interrupts, use the CX-Pro-
grammer to change the input’s setting in the PLC Setup.
Y CPU Units
The 6 input bits CIO 0.00 to CIO 0.01 and CIO 1.00 to CIO 1.03 can be used
for input interrupts.
Input Terminal Arrangement
Input terminal
block
Input operation setting
Task number
Word
Bit
Normal inputs
Input interrupt
CIO 0
00
Normal input 0
Input interrupt 0
Interrupt task 140
01
Normal input 1
Input interrupt 1
Interrupt task 141
02
Normal input 2
Input interrupt 2
Interrupt task 142
03
Normal input 3
Input interrupt 3
Interrupt task 143
04 to 11
Normal inputs 4 to 11
---
---
CIO 1
00
Normal input 12
Input interrupt 4
Interrupt task 144
01
Normal input 13
Input interrupt 5
Interrupt task 145
02
Normal input 14
Input interrupt 6
Interrupt task 146
03
Normal input 15
Input interrupt 7
Interrupt task 147
04 to 11
Normal inputs 16 to 23 ---
---
00
02
04 06 08 10 00
02
04 06 08 10
L1 L2/N
COM
01 03 05 07 09 11 01 03 05 07 09 11
LG
Input interrupt 0
Input interrupt 2
Input interrupt 3
Input interrupt 1
Input interrupt 7
Input interrupt 5
Input interrupt 4
Input interrupt 6
Inputs (CIO 0)
Inputs (CIO 1)
Upper Terminal Block
(Example: AC Power
Supply Modules)
NC
A0
−
B0
−
Z0
−
A1
−
B1
−
Z1
−
00
04 10 00
02
04
+
−
A0+ B0+ Z0+ A1+ B1+ Z1+ COM 01 05 11 01 03 05
Upper Terminal Block
Input
interrupt 3
Inputs (CIO 0)
Inputs (CIO 1)
Input
interrupt 5
Input
interrupt 4
Input
interrupt 2
Input
interrupt 0
Input
interrupt 1
High-speed counter terminals
High-speed counter terminals
Summary of Contents for CP1H CPU UNITS - PROGRAMMING 05-2007
Page 2: ......
Page 3: ...CP1H X40D CP1H XA40D CP1H Y20DT D CP1H CPU Unit Operation Manual Revised March 2009...
Page 4: ...iv...
Page 10: ...x...
Page 18: ...xviii...
Page 22: ...xxii...
Page 34: ...xxxiv Conformance to EC Directives 6...
Page 174: ...140 CP series Expansion I O Unit Wiring Section 3 6...
Page 370: ...336 Analog I O XA CPU Units Section 5 5...
Page 552: ...518 Trouble Shooting Section 8 7...
Page 595: ...561 Sample Application Section 9 12 Network Settings Network Tab Network Settings Driver Tab...
Page 598: ...564 Sample Application Section 9 12...
Page 642: ...608 Standard Models Appendix A...
Page 652: ...618 Dimensions Diagrams Appendix B...
Page 745: ...711 Connections to Serial Communications Option Boards Appendix F Connecting to Unit...
Page 746: ...712 Connections to Serial Communications Option Boards Appendix F...
Page 776: ...742 PLC Setup Appendix G...
Page 778: ...744 Specifications for External Power Supply Expansion Appendix H...
Page 786: ...752 Revision History...