209
High-speed Counters
Section 5-2
• The counting mode can be set to linear mode or circular (ring) mode.
• The counter reset method can be set to Z phase software reset,
software reset, Z phase software reset (continue comparing), or
software reset (continue comparing).
Pulse Input Functions
5-2-2
High-speed Counter Specifications
Specifications
Purpose
Function used
Description
Receive incremental rotary
encoder inputs to calculate
length or position.
High-speed counter
function
Built-in input terminals can be used for high-speed counter
inputs.
The PV for the high-speed counters are stored in the Auxiliary
Area.
The counters can be operated in ring mode or linear mode.
Measure a workpiece's length
or position.
(Start counting when a certain
condition is established or
pause counting when a certain
condition is established.)
High-speed Counter
Gate Bit
The high-speed counter can be started or stopped (PV held)
from the Unit's program by turning ON/OFF the High-speed
Counter Gate Bit when the desired condition is met.
Measure a workpiece's speed
from its position data (frequency
measurement.)
PRV(881) HIGH-
SPEED COUNTER
PV READ
The PRV(881) instruction can be used to measure the pulse fre-
quency.
• Range with differential phase inputs: 0 to 50 kHz (Y models: 0
to 500 kHz)
• Range with all other input modes: 0 to 100 kHz (Y models: 0 to
1 MHz)
PRV2(883) PULSE
FREQUENCY CON-
VERT
PRV2(883) reads the pulse frequency and converts it to a rota-
tional speed (r/min) or it converts the counter PV to a total num-
ber of rotations. Results are calculated by the number of pulses/
rotation.
Item
Specification
Number of high-speed counters
4 (High-speed counters 0 to 3)
Pulse input modes (Selected in the PLC
Setup)
Differential phase
inputs
Up/down inputs
Pulse + direction
inputs
Increment inputs
Input terminal allocation
Phase-A input
Increment pulse
input
Pulse input
Increment pulse
input
Phase-B input
Decrement pulse
input
Direction input
---
Phase-Z input
Reset input
Reset input
Reset input
Input method
Differential phase,
4x
(Fixed)
Two single-phase
inputs
Single-phase
pulse + direction
inputs
Single-phase
input
Response
frequency
X/XA
CPU
Unit
Counters
0 to 3
24 VDC
inputs
50 kHz
100 kHz
100 kHz
100 kHz
Y CPU
Unit
Counters
0 and 1
Line
driver
inputs
500 kHz
1 MHz
1 MHz
1 MHz
Counters
2 and 3
24 VDC
inputs
50 kHz
100 kHz
100 kHz
100 kHz
Counting mode
Linear mode or circular (ring) mode (Select in the PLC Setup.)
Summary of Contents for CP1H CPU UNITS - PROGRAMMING 05-2007
Page 2: ......
Page 3: ...CP1H X40D CP1H XA40D CP1H Y20DT D CP1H CPU Unit Operation Manual Revised March 2009...
Page 4: ...iv...
Page 10: ...x...
Page 18: ...xviii...
Page 22: ...xxii...
Page 34: ...xxxiv Conformance to EC Directives 6...
Page 174: ...140 CP series Expansion I O Unit Wiring Section 3 6...
Page 370: ...336 Analog I O XA CPU Units Section 5 5...
Page 552: ...518 Trouble Shooting Section 8 7...
Page 595: ...561 Sample Application Section 9 12 Network Settings Network Tab Network Settings Driver Tab...
Page 598: ...564 Sample Application Section 9 12...
Page 642: ...608 Standard Models Appendix A...
Page 652: ...618 Dimensions Diagrams Appendix B...
Page 745: ...711 Connections to Serial Communications Option Boards Appendix F Connecting to Unit...
Page 746: ...712 Connections to Serial Communications Option Boards Appendix F...
Page 776: ...742 PLC Setup Appendix G...
Page 778: ...744 Specifications for External Power Supply Expansion Appendix H...
Page 786: ...752 Revision History...