347
Serial Communications
Section 6-1
CPU Unit Serial Gateway Function Specifications
Note
If a CJ-series Serial Communications Unit is connected via a CJ Unit Adapter,
messages can also be converted to Modbus-ASCII or Host Link FINS. Refer
to the
SYSMAC CS/CJ Series Serial Communications Boards/Units Opera-
tion Manual
(W336) for details.
6-1-5
Serial PLC Links
Overview
Serial PLC Links can be used to allow data to be exchanged among CP1H
and CJ1M CPU Units via the RS-422A/485 or RS-232C Option Boards
mounted to the CPU Units without requiring special programming. The com-
munications mode in the PLC Setup must be set to the Serial PLC Link Mode
to enable this functionality.
• Either serial port 1 or 2 can be used. (See note.)
• Words are allocated in memory in the Serial PLC Link Words (CIO 3100
to CIO 3199).
• A maximum of 10 words can be transferred by each CPU1H CPU Unit,
but the number of linked words can be set to fewer words. (The size must
be the same for all CP1H CPU Units.)
Note
Serial PLC Links cannot be used on serial ports 1 and 2 at the same time. If
one port is set as a Serial PLC Link slave or master, it will not be possible to
set the other port for a Serial PLC Link. A PLC Setup error will occur if an
attempt is made to set both ports for Serial PLC Links.
Item
Specification
Pre-conversion data
FINS (via FINS network, Host Link FINS, toolbus, NT Link,
or CPU bus)
Conversion functions
FINS commands addressed to serial port 1 or 2 on the CPU
Unit are converted to CompoWay/F commands (after
removing the header) if the FINS command code is 2803
hex and to Modbus-RTU commands (after removing the
header) if the FINS command code is 2804 hex.
Post-conversion data
CompoWay/F command or Modbus-RTU command
Serial communications
method
1:N half-duplex
Maximum number of
nodes
31
Enabling serial commu-
nications mode
Serial Gateway Mode
Response timeout
The time from when a message converted to a different pro-
tocol is set until a response is received is monitored by the
serial gateway function.
Default: 5 s, User setting: 0.1 to 25.5 s
Note
A FINS response code of 0205 hex (response time-
out) is sent to the source of the FINS command if a
timeout occurs.
Send delay function
None
Summary of Contents for CP1H CPU UNITS - PROGRAMMING 05-2007
Page 2: ......
Page 3: ...CP1H X40D CP1H XA40D CP1H Y20DT D CP1H CPU Unit Operation Manual Revised March 2009...
Page 4: ...iv...
Page 10: ...x...
Page 18: ...xviii...
Page 22: ...xxii...
Page 34: ...xxxiv Conformance to EC Directives 6...
Page 174: ...140 CP series Expansion I O Unit Wiring Section 3 6...
Page 370: ...336 Analog I O XA CPU Units Section 5 5...
Page 552: ...518 Trouble Shooting Section 8 7...
Page 595: ...561 Sample Application Section 9 12 Network Settings Network Tab Network Settings Driver Tab...
Page 598: ...564 Sample Application Section 9 12...
Page 642: ...608 Standard Models Appendix A...
Page 652: ...618 Dimensions Diagrams Appendix B...
Page 745: ...711 Connections to Serial Communications Option Boards Appendix F Connecting to Unit...
Page 746: ...712 Connections to Serial Communications Option Boards Appendix F...
Page 776: ...742 PLC Setup Appendix G...
Page 778: ...744 Specifications for External Power Supply Expansion Appendix H...
Page 786: ...752 Revision History...