574
Error Classification and Confirmation
Section 11-1
11-1 Error Classification and Confirmation
Error Categories
Errors in CP1H CPU Units can be broadly divided into the following four cate-
gories.
Confirming Errors
There are three sources of information on errors that have occurred.
• CPU Unit indicators
• Seven-segment display
• Auxiliary Area
CPU Unit Indicators
These indicators show the operating status of the CPU Unit.
Note
Do not turn OFF the CPU Unit power supply when this indicator is lit.
Category
Comments
CPU Error
A WDT (watchdog timer) error is generated in the CPU Unit, the
CPU Unit will malfunction, and operation will stop.
CPU Standby
The CPU will go on standby because conditions for stating oper-
ation have not yet been met.
Fatal Error
Operation cannot continue. Operation will stop due to a serious
problem.
Non-fatal Error
A minor problem has occurred. Operation will continue
POWER
RUN
INH
PRPHL
BKUP
ERR/ALM
POWER
(green)
Lit
Power is ON.
Not lit
Power is OFF.
RUN (green)
Lit
The CPU Unit is executing a program in either RUN or
MONITOR mode.
Not lit
Operation is stopped in PROGRAM mode or due to a
fatal error.
ERR/ALM
(red)
Lit
A fatal error or CPU error (WDT error) has occurred.
operation will stop and all outputs will be turned OFF.
Flashing
A non-fatal error has occurred. Operation will continue.
Not lit
Operation is normal.
INH (yellow)
Lit
The Output OFF Bit (A500.15) was turned ON. All out-
puts will be turned OFF.
Not lit
Operation is normal.
BKUP
(yellow)
(See note.)
Lit
The built-in flash memory is being written to or the
Memory Cassette is being accessed.
The BKUP indicator also lights while the user program
is being restored when the power supply is turned ON.
Not lit
Other than the above.
PRPHL
(yellow)
Flashing
Communications (either sending or receiving) are in
progress through the peripheral port.
Not lit
Other than the above.
Summary of Contents for CP1H CPU UNITS - PROGRAMMING 05-2007
Page 2: ......
Page 3: ...CP1H X40D CP1H XA40D CP1H Y20DT D CP1H CPU Unit Operation Manual Revised March 2009...
Page 4: ...iv...
Page 10: ...x...
Page 18: ...xviii...
Page 22: ...xxii...
Page 34: ...xxxiv Conformance to EC Directives 6...
Page 174: ...140 CP series Expansion I O Unit Wiring Section 3 6...
Page 370: ...336 Analog I O XA CPU Units Section 5 5...
Page 552: ...518 Trouble Shooting Section 8 7...
Page 595: ...561 Sample Application Section 9 12 Network Settings Network Tab Network Settings Driver Tab...
Page 598: ...564 Sample Application Section 9 12...
Page 642: ...608 Standard Models Appendix A...
Page 652: ...618 Dimensions Diagrams Appendix B...
Page 745: ...711 Connections to Serial Communications Option Boards Appendix F Connecting to Unit...
Page 746: ...712 Connections to Serial Communications Option Boards Appendix F...
Page 776: ...742 PLC Setup Appendix G...
Page 778: ...744 Specifications for External Power Supply Expansion Appendix H...
Page 786: ...752 Revision History...