333
Analog I/O (XA CPU Units)
Section 5-5
Min. impedance 25MHz: 90
Ω
, 100 MHz : 160
Ω
Recommended installation method
(6) Refer to the following diagram regarding wiring disconnections when volt-
age input is being used.
Example: If analog input device 2 is outputting 5 V and the same power sup-
ply is being used for both devices as shown above, approximately 1/3, or 1.6
V, will be applied to the input for input device 1.
If a wiring disconnection occurs when voltage input is being used, the situa-
tion described below will result. Either separate the power supplies for the
connected devices, or use an isolator for each input.
30
32
33
24 VDC
A
C
B
Analog
input
device 1
Analog
input
device 2
Summary of Contents for CP1H CPU UNITS - PROGRAMMING 05-2007
Page 2: ......
Page 3: ...CP1H X40D CP1H XA40D CP1H Y20DT D CP1H CPU Unit Operation Manual Revised March 2009...
Page 4: ...iv...
Page 10: ...x...
Page 18: ...xviii...
Page 22: ...xxii...
Page 34: ...xxxiv Conformance to EC Directives 6...
Page 174: ...140 CP series Expansion I O Unit Wiring Section 3 6...
Page 370: ...336 Analog I O XA CPU Units Section 5 5...
Page 552: ...518 Trouble Shooting Section 8 7...
Page 595: ...561 Sample Application Section 9 12 Network Settings Network Tab Network Settings Driver Tab...
Page 598: ...564 Sample Application Section 9 12...
Page 642: ...608 Standard Models Appendix A...
Page 652: ...618 Dimensions Diagrams Appendix B...
Page 745: ...711 Connections to Serial Communications Option Boards Appendix F Connecting to Unit...
Page 746: ...712 Connections to Serial Communications Option Boards Appendix F...
Page 776: ...742 PLC Setup Appendix G...
Page 778: ...744 Specifications for External Power Supply Expansion Appendix H...
Page 786: ...752 Revision History...