676
Auxiliary Area Allocations by Address
Appendix D
A621 to
A635
A621.00
to
A635.04
Communica-
tions Units 0
to 15, Ports
1 to 4 Set-
tings Chang-
ing Flag
Same as above.
ON: Changing
OFF: Not
changing
Retained Cleared
---
---
A640
A640.00 Serial Port 2
Modbus-
RTU Easy
Master Exe-
cution Bit
Turn ON this bit to send a command
and receive a response for serial port 2
using the Modbus-RTU easy master
function.
This bit will be turned OFF automatically
by the system when communications
have been completed.
Turned ON:
Execution
started
ON: Execution
in progress.
OFF: Not exe-
cuted or execu-
tion completed.
Retained Cleared
---
DM fixed
alloca-
tion
words for
Modbus-
RTU
Easy
Master:
D32300
to
D32399
A640.01 Serial Port 2
Modbus-
RTU Easy
Master Nor-
mal End
Flag
ON when one command has been sent
and the response received for serial
port 2 using the Modbus-RTU easy
master function.
ON: Execution
normal.
OFF: Execution
error or still in
progress.
Retained Cleared
---
A640.02 Serial Port 2
Modbus-
RTU Easy
Master Error
End Flag
ON when an error has occurred in com-
munications for serial port 2 using the
Modbus-RTU easy master function.
The error code is output to D32252 in
the DM fixed allocation words for Mod-
bus-RTU Easy Master.
ON: Execution
error.
OFF: Execution
normal or still
in progress.
Retained Cleared
---
A641
A641.00 Serial Port 1
Modbus-
RTU Master
Execution
Bit
Turn ON this bit to send a command
and receive a response for serial port 1
using the Modbus-RTU easy master
function.
This bit will be turned OFF automatically
by the system when communications
have been completed.
Turned ON:
Execution
started
ON: Execution
in progress.
OFF: Not exe-
cuted or execu-
tion completed.
Retained Cleared
---
DM fixed
alloca-
tion
words for
Modbus-
RTU
Easy
Master:
D32200
to
D32299
A641.01 Serial Port 1
Modbus-
RTU Master
Execution
Normal Flag
ON when one command has been sent
and the response received for serial
port 1 using the Modbus-RTU easy
master function.
ON: Execution
normal.
OFF: Execution
error or still in
progress.
Retained Cleared
---
A641.02 Serial Port 1
Modbus-
RTU Master
Execution
Error Flag
ON when an error has occurred in com-
munications for serial port 1 using the
Modbus-RTU easy master function.
The error code is output to D32352 in
the DM fixed allocation words for Mod-
bus-RTU Easy Master.
ON: Execution
error.
OFF: Execution
normal or still
in progress.
Retained Cleared
---
A642
All
Analog
Adjustment
PV
Stores the value set on the analog
adjuster as a hexadecimal value (reso-
lution: 1/256).
0000 to 00FF
hex
Retained Cleared
---
---
A643
All
External
Analog Set-
ting Input
PV
Stores the value set from the external
analog setting input as a hexadecimal
value (resolution: 1/256).
0000 to 00FF
hex
Retained Cleared
---
---
A651
All
Program
Password
Type in the password to replace a pro-
gram.
A5A5 hex: Replacement Start Bit
(A65015) is enabled.
Any other value: Replacement Start Bit
(A65015) is disabled.
When the power is turned ON or pro-
gram replacement is completed, the
Replacement Start Bit will be turned
OFF, regardless of whether replace-
ment was completed normally or in
error.
---
Retained Cleared
---
---
Addresses
Name
Function
Settings
Status
after
mode
change
Status
at star-
tup
Write
timing
Related
Flags,
Settings
Word
Bits
Summary of Contents for CP1H CPU UNITS - PROGRAMMING 05-2007
Page 2: ......
Page 3: ...CP1H X40D CP1H XA40D CP1H Y20DT D CP1H CPU Unit Operation Manual Revised March 2009...
Page 4: ...iv...
Page 10: ...x...
Page 18: ...xviii...
Page 22: ...xxii...
Page 34: ...xxxiv Conformance to EC Directives 6...
Page 174: ...140 CP series Expansion I O Unit Wiring Section 3 6...
Page 370: ...336 Analog I O XA CPU Units Section 5 5...
Page 552: ...518 Trouble Shooting Section 8 7...
Page 595: ...561 Sample Application Section 9 12 Network Settings Network Tab Network Settings Driver Tab...
Page 598: ...564 Sample Application Section 9 12...
Page 642: ...608 Standard Models Appendix A...
Page 652: ...618 Dimensions Diagrams Appendix B...
Page 745: ...711 Connections to Serial Communications Option Boards Appendix F Connecting to Unit...
Page 746: ...712 Connections to Serial Communications Option Boards Appendix F...
Page 776: ...742 PLC Setup Appendix G...
Page 778: ...744 Specifications for External Power Supply Expansion Appendix H...
Page 786: ...752 Revision History...