Analog I/O (XA CPU Units)
Section 5-5
1. Setting the Analog Voltage/Current Input Switches
Each analog input can be set for use as a voltage input or current input.
Each input’s input range is set independently in the PLC Setup. The voltage
input range can be set to 0 to 5 V, 1 to 5 V, 0 to 10 V, or
−
10 to 10 V. The cur-
rent input range can be set to 0 to 20 mA or 4 to 20 mA.
Note
The built-in analog input switch is located on the PCB inside the case. To
make setting the switch easier, make the switch settings before mounting the
terminal block to the base.
When setting this switch, be very careful not to damage the wiring on the
PCB.
2. PLC Setup
Use the CX-Programmer to set the various PLC Setup including whether the I/
O point is being used, the input range, output range, averaging function
usage, and resolution. The I/O point usage, input range, output range, and
averaging function usage can be set independently for each I/O point, but the
resolution setting applies to all of the I/O points.
• The input range can be set to
−
10 to 10 V, 0 to 10 V, 1 to 5 V, 0 to 5 V, 0 to
20 mA or 4 to 20 mA.
• The output range can be set to
−
10 to 10 V, 0 to 10 V, 1 to 5 V, 0 to 5 V, 0
to 20 mA or 4 to 20 mA.
• Once the range has been set, it cannot be changed as long as the CP1H
CPU Unit’s power is ON. To change the input range or output range,
change the setting in the PLC Setup, turn the CPU Unit OFF, and then
turn the CPU Unit ON again.
ON
1
2
3
4
ON
OFF
Analog input 4 selection switch
Analog input 3 selection switch
Analog input 2 selection switch
Analog input 1 selection switch
OFF: Voltage input (factory default setting)
ON: Current input
Summary of Contents for CP1H CPU UNITS - PROGRAMMING 05-2007
Page 2: ......
Page 3: ...CP1H X40D CP1H XA40D CP1H Y20DT D CP1H CPU Unit Operation Manual Revised March 2009...
Page 4: ...iv...
Page 10: ...x...
Page 18: ...xviii...
Page 22: ...xxii...
Page 34: ...xxxiv Conformance to EC Directives 6...
Page 174: ...140 CP series Expansion I O Unit Wiring Section 3 6...
Page 370: ...336 Analog I O XA CPU Units Section 5 5...
Page 552: ...518 Trouble Shooting Section 8 7...
Page 595: ...561 Sample Application Section 9 12 Network Settings Network Tab Network Settings Driver Tab...
Page 598: ...564 Sample Application Section 9 12...
Page 642: ...608 Standard Models Appendix A...
Page 652: ...618 Dimensions Diagrams Appendix B...
Page 745: ...711 Connections to Serial Communications Option Boards Appendix F Connecting to Unit...
Page 746: ...712 Connections to Serial Communications Option Boards Appendix F...
Page 776: ...742 PLC Setup Appendix G...
Page 778: ...744 Specifications for External Power Supply Expansion Appendix H...
Page 786: ...752 Revision History...