593
Troubleshooting Unit Errors
Section 11-4
Input irregularly turns ON/
OFF.
(1) External input voltage is low or unstable. Adjust external input voltage to within rated
range.
(2) Malfunction due to noise.
Take protective measures against noise,
such as:
• Install surge suppressor.
• Install insulation transformer.
Install shielded cables between the Input
Unit and the loads.
(3) Terminal block screws are loose.
Tighten screws
(4) Faulty terminal block connector contact.
Replace terminal block connector.
Error occurs in units of
8 points or 16 points, i.e., for
the same common.
(1) Common terminal screws are loose.
Tighten screws
(2) Faulty terminal block connector contact.
Replace terminal block connector.
(3) Faulty data bus
Replace Unit.
(4) Faulty CPU
Replace CPU Unit.
Input indicator is not lit in nor-
mal operation.
Faulty indicator or indicator circuit.
Replace Unit.
Symptom
Cause
Remedy
Summary of Contents for CP1H CPU UNITS - PROGRAMMING 05-2007
Page 2: ......
Page 3: ...CP1H X40D CP1H XA40D CP1H Y20DT D CP1H CPU Unit Operation Manual Revised March 2009...
Page 4: ...iv...
Page 10: ...x...
Page 18: ...xviii...
Page 22: ...xxii...
Page 34: ...xxxiv Conformance to EC Directives 6...
Page 174: ...140 CP series Expansion I O Unit Wiring Section 3 6...
Page 370: ...336 Analog I O XA CPU Units Section 5 5...
Page 552: ...518 Trouble Shooting Section 8 7...
Page 595: ...561 Sample Application Section 9 12 Network Settings Network Tab Network Settings Driver Tab...
Page 598: ...564 Sample Application Section 9 12...
Page 642: ...608 Standard Models Appendix A...
Page 652: ...618 Dimensions Diagrams Appendix B...
Page 745: ...711 Connections to Serial Communications Option Boards Appendix F Connecting to Unit...
Page 746: ...712 Connections to Serial Communications Option Boards Appendix F...
Page 776: ...742 PLC Setup Appendix G...
Page 778: ...744 Specifications for External Power Supply Expansion Appendix H...
Page 786: ...752 Revision History...