114
Mounting
Section 3-3
• Slide the yellow sliders at the top and bottom of each Unit to lock the
Units together.
Note
If the sliders are not secured properly, the Unit may not function properly.
3.
Attach the End Cover to the Unit on the far right side of the Rack.
Note
Attach the End Cover to the Unit on the far right side of the Rack. An I/O bus
error will occur and CP1H CPU Unit will not operate in either RUN or MONI-
TOR mode if the End Cover is not connected. If this occurs, the following infor-
mation will be set in memory.
• Always turn OFF the power supply before connecting Units to each
other.
3-3-4
DIN Track Installation
1,2,3...
1.
Use a screwdriver to pull down the DIN Track mounting pins from the back
of the Units, and mount the Units to the DIN Track.
Move the sliders toward the
back until they lock into place.
Lock
Release
Slider
Name
Address
Status
I/O Bus Error Flag
A401.14
ON
I/O Bus Error Details
A404
0E0E hex
Summary of Contents for CP1H CPU UNITS - PROGRAMMING 05-2007
Page 2: ......
Page 3: ...CP1H X40D CP1H XA40D CP1H Y20DT D CP1H CPU Unit Operation Manual Revised March 2009...
Page 4: ...iv...
Page 10: ...x...
Page 18: ...xviii...
Page 22: ...xxii...
Page 34: ...xxxiv Conformance to EC Directives 6...
Page 174: ...140 CP series Expansion I O Unit Wiring Section 3 6...
Page 370: ...336 Analog I O XA CPU Units Section 5 5...
Page 552: ...518 Trouble Shooting Section 8 7...
Page 595: ...561 Sample Application Section 9 12 Network Settings Network Tab Network Settings Driver Tab...
Page 598: ...564 Sample Application Section 9 12...
Page 642: ...608 Standard Models Appendix A...
Page 652: ...618 Dimensions Diagrams Appendix B...
Page 745: ...711 Connections to Serial Communications Option Boards Appendix F Connecting to Unit...
Page 746: ...712 Connections to Serial Communications Option Boards Appendix F...
Page 776: ...742 PLC Setup Appendix G...
Page 778: ...744 Specifications for External Power Supply Expansion Appendix H...
Page 786: ...752 Revision History...