157
Built-in Analog I/O Area (XA CPU Units Only)
Section 4-3
4-3
Built-in Analog I/O Area (XA CPU Units Only)
Built-in Analog Input Bits:
CIO 200 to CIO 203 (4 words)
Built-in Analog Output Bits:
CIO 210 to CIO 211 (2 words)
The built-in analog inputs and built-in analog outputs for XA CPU Units are
always allocated words between CIO 200 and CIO 211.
The Analog I/O Area will be cleared at the following times:
1.
When the operating mode is changed between PROGRAM and RUN or
MONITOR mode (See note.)
2.
When the power is cycled
3.
When analog I/O memory is cleared from the CX-Programmer
4.
When operation fails due to a fatal error other than one created by execut-
ing a FALS(007) instruction (Memory will be retained if operation fails due
to execution of a FALS(007) instruction.)
Note
The built-in analog outputs will operate as follows when the operating mode is
switched between RUN or MONITOR mode and PROGRAM mode:
Note
Control of the built-in analog outputs will temporarily stop when Memory Cas-
sette data is being transferred or verified. Therefore, if the operating mode is
switched between PROGRAM and RUN or MONITOR mode when the built-in
analog output is being used and the I/O Memory Hold Bit is set to ON to retain
analog values output externally, the values will change; the analog values out-
put externally will not be retained while Memory Cassette data is being trans-
ferred or verified. The analog output values will return to the original retained
values when the transfer or verification has been completed.
Data
Allocated
words
Description
Data
1/6000
resolution
1/12000
resolution
Analog input
A/D conversion
data
CIO 200
Analog input 0
−
10 to 10 V:
F448 to 0BB8
hex
Other ranges:
0000 to 1770 hex
−
10 to 10 V:
E890 to 1770 hex
Other ranges:
0000 to 2EE0
hex
CIO 201
Analog input 1
CIO 202
Analog input 2
CIO 203
Analog input 3
Analog output
D/A conversion
data
CIO 210
Analog output 0
CIO 211
Analog output 1
I/O Memory Hold Bit
(A500.12)
Operation
OFF
The analog output values in the words allocated in
memory will be cleared and the 0000 hex will be output
for the output refresh.
ON
The analog output values in the words allocated in
memory will retain their values from right before the
operating mode was changed and the previous values
will be output for the output refresh.
Summary of Contents for CP1H CPU UNITS - PROGRAMMING 05-2007
Page 2: ......
Page 3: ...CP1H X40D CP1H XA40D CP1H Y20DT D CP1H CPU Unit Operation Manual Revised March 2009...
Page 4: ...iv...
Page 10: ...x...
Page 18: ...xviii...
Page 22: ...xxii...
Page 34: ...xxxiv Conformance to EC Directives 6...
Page 174: ...140 CP series Expansion I O Unit Wiring Section 3 6...
Page 370: ...336 Analog I O XA CPU Units Section 5 5...
Page 552: ...518 Trouble Shooting Section 8 7...
Page 595: ...561 Sample Application Section 9 12 Network Settings Network Tab Network Settings Driver Tab...
Page 598: ...564 Sample Application Section 9 12...
Page 642: ...608 Standard Models Appendix A...
Page 652: ...618 Dimensions Diagrams Appendix B...
Page 745: ...711 Connections to Serial Communications Option Boards Appendix F Connecting to Unit...
Page 746: ...712 Connections to Serial Communications Option Boards Appendix F...
Page 776: ...742 PLC Setup Appendix G...
Page 778: ...744 Specifications for External Power Supply Expansion Appendix H...
Page 786: ...752 Revision History...