397
Analog Input Units
Section 7-2
■
Set Data
• The Analog Input Unit will not start converting analog I/O values until the
range code has been written.
• Once the range code has been set, it is not possible to change the setting
while power is being supplied to the CPU Unit. To change the I/O range,
turn the CPU Unit OFF then ON again.
Averaging
Set whether averaging is to be used for set data. When the averaging bit is set
to 1, the average (moving average) for the past eight inputs is output as con-
version data.
Reading Analog Input
Conversion Values
Read the conversion value storage area with the ladder program. With word m
as the last input word allocated to the CPU Unit or an already-connected
Expansion Unit, the A/D conversion data will be output to the following words
m+1 to m+4.
Startup Operation
After the power is turned ON, it will require two cycle times plus approximately
50 ms before the first conversion data is stored in the input words. Therefore,
create a program as shown below, so that when operation begins simulta-
neously with startup it will wait for valid conversion data.
The analog input data will be 0000 until the initial processing is completed.
Handling Unit Errors
• When an error occurs in an Analog Input Unit, the analog input conversion
data becomes 0000.
15 0
1 0 0 0 0 0 0
8 7 6 5 4 3 2 1
15 0
1 0 0 0 0 0 0
8 7 6 5 4 3 2 1
0
0
Set to 1.
Set to 1.
Wd (n+1)
Wd (n+2)
Analog input 1
Analog input 2
Analog input 3
Analog input 4
Averaging
0
No
1
Yes
Input Use
0
No
1
Yes
Range code
Analog input signal range
−
10 to 10 V
0 to 10 V
1 to 5 V or 4 to 20 mA
0 to 5 V or 0 to 20 mA
00
01
10
11
MOV(021)
2
D 0
T 5
#0002
T5
Power ON
P_On
TIM5 is started when the power is
turned ON. After 0.1 to 0.2 s (100 to
200 ms) elapses, the TIM5 contact
turns ON and the analog input 1 con-
version data stored in word 2 is trans-
ferred to DM0.
Summary of Contents for CP1H CPU UNITS - PROGRAMMING 05-2007
Page 2: ......
Page 3: ...CP1H X40D CP1H XA40D CP1H Y20DT D CP1H CPU Unit Operation Manual Revised March 2009...
Page 4: ...iv...
Page 10: ...x...
Page 18: ...xviii...
Page 22: ...xxii...
Page 34: ...xxxiv Conformance to EC Directives 6...
Page 174: ...140 CP series Expansion I O Unit Wiring Section 3 6...
Page 370: ...336 Analog I O XA CPU Units Section 5 5...
Page 552: ...518 Trouble Shooting Section 8 7...
Page 595: ...561 Sample Application Section 9 12 Network Settings Network Tab Network Settings Driver Tab...
Page 598: ...564 Sample Application Section 9 12...
Page 642: ...608 Standard Models Appendix A...
Page 652: ...618 Dimensions Diagrams Appendix B...
Page 745: ...711 Connections to Serial Communications Option Boards Appendix F Connecting to Unit...
Page 746: ...712 Connections to Serial Communications Option Boards Appendix F...
Page 776: ...742 PLC Setup Appendix G...
Page 778: ...744 Specifications for External Power Supply Expansion Appendix H...
Page 786: ...752 Revision History...