731
PLC Setup
Appendix G
Define Origin Operation Settings: Origin Search Settings
Name
Default
Settings
When setting is read
by CPU Unit
Internal
address
Bits
Settings
1
Use define origin opera-
tion
Do not use.
Do not use.
When power is turned
ON
274
00 to
03
0 hex
Use. 1
hex
1-1
Search Direction
CW
CW
At start of operation
275
12 to
15
0 hex
CCW
1 hex
1-2
Detection Method Method 0
Method 0
At start of operation
275
08 to
11
0 hex
Method 1
1 hex
Method 2
2 hex
1-3
Search Operation Inverse 1
Inverse 1
At start of operation
275
04 to
07
0 hex
Inverse 2
1 hex
1-4
Operation Mode
Mode 0
Mode 0
At start of operation
275
00 to
03
0 hex
Mode 1
1 hex
Mode 2
2 hex
1-5
Origin Input Sig-
nal
(X/XA CPU Units)
NC
NC
Unit version 1.0 and
earlier: At start of
operation
Unit version 1.1 and
later: When power is
turned ON
286
08 to
11
0 hex
NO
1 hex
Origin Input Sig-
nal
(Y CPU Units)
NC (line driver)
At start of operation
2 hex
NO (line driver)
3 hex
1-6
Proximity Input
Signal
NC
NC
At start of operation
286
04 to
07
0 hex
NO
1 hex
1-7
Search High
Speed
0 pps
(disabled)
0 pps
At start of operation
279 and
278
00 to
15
0000 0001
hex
:
:
100,000 pps (maximum
for X/XA CPU
Unit)1,000,00 0 pps
(maximum for Y CPU
Unit)
0001 86A0
hex
000F 4240
hex
1-8
Search Proximity
Speed
0 pps
(disabled)
1 pps
At start of operation
281 and
280
00 to
15
0000 0001
hex
:
:
100,000 pps (maximum
for X/XA CPU
Unit)1,000,00 0 pps
(maximum for Y CPU
Unit)
0001 86A0
hex
000F 4240
hex
1-9
Search Compen-
sation Value
0 pps
−
2,147,483,648
At start of operation
283 and
282
00 to
15
8000 0000
hex
:
:
0
0000 0000
hex
:
:
+2,147,483,647
7FFF FFFF
hex
1-10
Search Accelera-
tion Ratio
0 (disabled)
1 (pulses/4 ms)
At start of operation
284
00 to
15
0001 hex
:
:
65,535 (pulses/4 ms)
FFFF hex
1-11
Search Decelera-
tion Ratio
0 (disabled)
1 (pulses/4 ms)
At start of operation
285
00 to
15
0001 hex
:
:
65,535 (pulses/4 ms)
FFFF hex
1-12
Positioning Moni-
tor Time
0 ms
0 ms
At start of operation
287
00 to
15
0000 hex
:
:
9,999 ms
270F hex
Summary of Contents for CP1H CPU UNITS - PROGRAMMING 05-2007
Page 2: ......
Page 3: ...CP1H X40D CP1H XA40D CP1H Y20DT D CP1H CPU Unit Operation Manual Revised March 2009...
Page 4: ...iv...
Page 10: ...x...
Page 18: ...xviii...
Page 22: ...xxii...
Page 34: ...xxxiv Conformance to EC Directives 6...
Page 174: ...140 CP series Expansion I O Unit Wiring Section 3 6...
Page 370: ...336 Analog I O XA CPU Units Section 5 5...
Page 552: ...518 Trouble Shooting Section 8 7...
Page 595: ...561 Sample Application Section 9 12 Network Settings Network Tab Network Settings Driver Tab...
Page 598: ...564 Sample Application Section 9 12...
Page 642: ...608 Standard Models Appendix A...
Page 652: ...618 Dimensions Diagrams Appendix B...
Page 745: ...711 Connections to Serial Communications Option Boards Appendix F Connecting to Unit...
Page 746: ...712 Connections to Serial Communications Option Boards Appendix F...
Page 776: ...742 PLC Setup Appendix G...
Page 778: ...744 Specifications for External Power Supply Expansion Appendix H...
Page 786: ...752 Revision History...