580
Troubleshooting
Section 11-2
11-2-1 Error Processing Flowchart
Confirm the error category by referring to the status of the CPU Unit indicators
and the 7-segment display, investigate the cause for the error in the error
tables, and take corrective actions.
11-2-2 No Operation When Power Is Supplied
First confirm that the POWER indicator (green) is lit.
POWER Indicator Not Lit
The power supply may not match the Unit rating, wiring may not be correct, or
the Unit may be faulty.
1,2,3...
1.
Confirm the Unit rating (i.e., is it 24 VDC or 100 to 240 VAC?) and see if
the supply power matches the rating.
2.
Check the wiring to see if it is correct and that nothing is disconnected.
3.
Check the voltage at the power supply terminals. If the voltage is normal
and the POWER indicator is lit, the Unit may be faulty. In that case, replace
the Unit.
POWER Indicator Turns OFF and ON
There may be fluctuations in the power supply voltage, disconnected wiring,
or poor contacts. Check the power supply system and wiring.
POWER Indicator Lit but No Operation
Check the RUN indicator if the POWER indicator is lit but the CPU Unit does
not operate. The CPU Unit may be on standby if the RUN indicator is not lit.
■
CPU Standby
Detection of Special I/O Units and CPU Bus Units has not been completed.
• If a CPU Bus Unit has not started normally, check the Unit Setup.
• If a Special I/O Unit is not detected, replace the Special I/O Unit.
Error occurred.
POWER indicator lit?
RUN indicator lit?
ERR/ALM indicator lit?
Information on
7-segment display?
There is no error
in the CP1H.
Check for other
causes (section
11-3).
Check the power supply
(sections 11-2-2 and 11-3).
ERR/ALM indicator lit?
A CPU standby
error has
occurred.
Refer to
section 11-2-2.
A non-fatal error has occurred.
Refer to section 11-2-5.
A fatal error has occurred.
Refer to section 11-2-3.
A CPU error has occurred.
Refer to section 11-2-4.
Lit
Not lit
The display is not
lit or is frozen.
Not lit
The display is
being updated.
Not lit
Flashing
Not lit
Lit
Not lit
Lit
The display is
being updated.
Information on
7-segment display?
Summary of Contents for CP1H CPU UNITS - PROGRAMMING 05-2007
Page 2: ......
Page 3: ...CP1H X40D CP1H XA40D CP1H Y20DT D CP1H CPU Unit Operation Manual Revised March 2009...
Page 4: ...iv...
Page 10: ...x...
Page 18: ...xviii...
Page 22: ...xxii...
Page 34: ...xxxiv Conformance to EC Directives 6...
Page 174: ...140 CP series Expansion I O Unit Wiring Section 3 6...
Page 370: ...336 Analog I O XA CPU Units Section 5 5...
Page 552: ...518 Trouble Shooting Section 8 7...
Page 595: ...561 Sample Application Section 9 12 Network Settings Network Tab Network Settings Driver Tab...
Page 598: ...564 Sample Application Section 9 12...
Page 642: ...608 Standard Models Appendix A...
Page 652: ...618 Dimensions Diagrams Appendix B...
Page 745: ...711 Connections to Serial Communications Option Boards Appendix F Connecting to Unit...
Page 746: ...712 Connections to Serial Communications Option Boards Appendix F...
Page 776: ...742 PLC Setup Appendix G...
Page 778: ...744 Specifications for External Power Supply Expansion Appendix H...
Page 786: ...752 Revision History...