662
Auxiliary Area Allocations by Address
Appendix D
A401
A401.14 I/O Bus Error
Flag
(fatal error)
ON in the following cases:
• When an error occurs in a data
transfer between the CPU Unit
and a CP-series Expansion Unit or
Expansion I/O Unit. If this hap-
pens, 0A0A hex will be output to
A404.
• When an error occurs in a data
transfer between the CPU Unit
and a CJ-series Unit. If this hap-
pens, 0000 hex will be output to
A404 to indicate the first Unit,
0001 hex to indicate the second
Unit, and 0F0F hex to indicate an
undetermined Unit.
• When the End Cover is not
attached to the last CJ-series Unit.
If this happens, 0E0E hex will be
output to A404.
CPU Unit operation will stop and the
ERR/ALM indicator on the front of
the CPU Unit will light.
(This flag will be turned OFF when
the error is cleared.)
ON: Error
OFF: No error
Cleared
Cleared
Refreshed
when error
occurs.
A404
A401.15 Memory Error
Flag
(fatal error)
ON when an error occurred in mem-
ory or there was an error in auto-
matic transfer from the Memory
Cassette when the power was turned
ON.
CPU Unit operation will stop and the
ERR/ALM indicator on the front of
the CPU Unit will light.
The location where the error
occurred is indicated in A403.00 to
A403.08, and A403.09 will be turned
ON if there was an error during auto-
matic transfer at startup.
This flag will be turned OFF when
the error is cleared. (The automatic
transfer at startup error cannot be
cleared without turning OFF the
PLC.)
ON: Error
OFF: No error
Cleared
Cleared
Refreshed
when error
occurs.
A403.00
to
A403.08,
A403.09
A402
A402.00 Other Fatal
Error Flag
ON when a non-fatal error that is not
defined for A402.01 to A402.15
occurs. Detailed information is output
to the bits of A314.
There are no errors that affect this
flag at this time. This flag is reserved
by the system.
OFF: No
other fatal
error
ON: Other
fatal error
Cleared
Cleared
Refreshed
when error
occurs.
A315
A402.04 Battery Error
Flag
(non-fatal
error)
ON if the CPU Unit’s battery is dis-
connected or its voltage is low and
the Detect Battery Error setting has
been set in the PLC Setup.
The CPU Unit will continue operating
and the ERR/ALM indicator on the
front of the CPU Unit will flash.
This flag can be used to control an
external warning light or other indica-
tor to indicate that the battery needs
to be replaced.
(This flag will be turned OFF when
the error is cleared.)
ON: Error
OFF: No error
Cleared
Cleared
Refreshed
when error
occurs.
PLC
Setup
(Detect
Battery
Error)
Address
Name
Function
Settings
Status
after
mode
change
Status
at star-
tup
Write
timing
Related
flags, set-
tings
Words
Bits
Summary of Contents for CP1H CPU UNITS - PROGRAMMING 05-2007
Page 2: ......
Page 3: ...CP1H X40D CP1H XA40D CP1H Y20DT D CP1H CPU Unit Operation Manual Revised March 2009...
Page 4: ...iv...
Page 10: ...x...
Page 18: ...xviii...
Page 22: ...xxii...
Page 34: ...xxxiv Conformance to EC Directives 6...
Page 174: ...140 CP series Expansion I O Unit Wiring Section 3 6...
Page 370: ...336 Analog I O XA CPU Units Section 5 5...
Page 552: ...518 Trouble Shooting Section 8 7...
Page 595: ...561 Sample Application Section 9 12 Network Settings Network Tab Network Settings Driver Tab...
Page 598: ...564 Sample Application Section 9 12...
Page 642: ...608 Standard Models Appendix A...
Page 652: ...618 Dimensions Diagrams Appendix B...
Page 745: ...711 Connections to Serial Communications Option Boards Appendix F Connecting to Unit...
Page 746: ...712 Connections to Serial Communications Option Boards Appendix F...
Page 776: ...742 PLC Setup Appendix G...
Page 778: ...744 Specifications for External Power Supply Expansion Appendix H...
Page 786: ...752 Revision History...