78
CP1H CPU Unit Operation
Section 2-3
2-3-2
Flash Memory Data Transfers
Built-in Flash Memory
Writing to Flash Memory
Data
Transfer method
User program and
parameter data
This data is automatically transferred from RAM to flash mem-
ory when a project is transferred from the CX-Programmer,
when the data is written to RAM from a PT or other external
device, or when the data is transferred from a Memory Cas-
sette.
DM Area data
This data is transferred to flash memory only when the trans-
fer is specified from the CX-Programmer.
Comment memory
data
This data is written to flash memory when a project is trans-
ferred from the CX-Programmer and transferring comment
memory is specified.
Function block
source data
This data is written to flash memory when a project containing
one or more function blocks is transferred from the CX-Pro-
grammer.
RAM
Write operation from CX-Programmer
or automatic transfer from Memory
Cassette at startup.
Write
Write
User program
area
Parameter area
I/O memory area
DM Area
Battery
Backup
Write (comment memory specified)
Write
Automatic write
Automatic write
Write
Built-in flash memory
User program
area
Parameter area
DM Area initial
values
Comment memory
area
FB source memory
area
CPU Unit
FB = Function block
Write operation
to flash memory
Summary of Contents for CP1H CPU UNITS - PROGRAMMING 05-2007
Page 2: ......
Page 3: ...CP1H X40D CP1H XA40D CP1H Y20DT D CP1H CPU Unit Operation Manual Revised March 2009...
Page 4: ...iv...
Page 10: ...x...
Page 18: ...xviii...
Page 22: ...xxii...
Page 34: ...xxxiv Conformance to EC Directives 6...
Page 174: ...140 CP series Expansion I O Unit Wiring Section 3 6...
Page 370: ...336 Analog I O XA CPU Units Section 5 5...
Page 552: ...518 Trouble Shooting Section 8 7...
Page 595: ...561 Sample Application Section 9 12 Network Settings Network Tab Network Settings Driver Tab...
Page 598: ...564 Sample Application Section 9 12...
Page 642: ...608 Standard Models Appendix A...
Page 652: ...618 Dimensions Diagrams Appendix B...
Page 745: ...711 Connections to Serial Communications Option Boards Appendix F Connecting to Unit...
Page 746: ...712 Connections to Serial Communications Option Boards Appendix F...
Page 776: ...742 PLC Setup Appendix G...
Page 778: ...744 Specifications for External Power Supply Expansion Appendix H...
Page 786: ...752 Revision History...