268
Pulse Outputs
Section 5-3
An origin search will not be started unless the origin search proximity speed is
less than the origin search high speed and unless the origin search/return ini-
tial speed is less than the origin search proximity speed.
Origin Search Error Processing
The CP1H CPU Unit's pulse output function performs a basic error check
before starting to output pulses (when the instruction is executed) and will not
output pulses if the settings are incorrect. There are other errors that can
occur with the origin search function during pulse output, which may stop the
pulse output.
If an error occurs that stops pulse output, the pulse output's Output Stopped
Error Flag will be turned ON and the Pulse Output Stop Error Code will be
written to Error Code word. Use these flags and error codes to identify the
cause of the error.
The Pulse Output Stop Errors will not affect the CPU Unit's operating status.
(The Pulse Output Stop Errors do not cause a fatal or non-fatal error in the
CPU Unit.)
Related Auxiliary Area Flags)
Pulse Output Stop Error Codes
Positioning with absolute
pulse specification
Cannot be used.
Positioning with relative
pulse specification
Outputs the specified number of pulses after setting the
current position to 0.
Function
Operation
Function
Pulse output number
0
1
2
3
Output Stopped Error Flags
ON when an error occurred while outputting
pulses in the origin search function.
0: No error
1: Stop error occurred.
A280.07
A281.07
A326.07
A327.07
Stop Error Codes
When a Pulse Output Stop Error occurs, the error code is stored in that
pulse outputs corresponding Stop Error Code word.
A444
A445
A438
A439
Error name
Error code
Likely cause
Corrective action
Operation after
error
CW Limit Stop Input
Signal
0100
Stopped due to a CW limit signal
input.
Move in the CCW direction.
Immediate stop,
No effect on
other port
CCW Limit Stop
Input Signal
0101
Stopped due to a CCW limit sig-
nal input.
Move in the CW direction.
No Origin Proximity
Input Signal
0200
The parameters indicate that the
Origin Proximity Input Signal is
being used, but a Origin Proxim-
ity Input Signal was not received
during the origin search.
Check the wiring of the Origin
Proximity Input Signal as well as
the PLC Setup's Origin Proxim-
ity Input Signal Type setting (NC
or NO) and execute the origin
search again. Turn the power
supply OFF and then ON if the
signal type setting was changed.
No effect on
other port
No Origin Input Sig-
nal
0201
The Origin Input Signal was not
received during the origin
search.
Check the wiring of the Origin
Input Signal as well as the PLC
Setup's Origin Input Signal Type
setting (NC or NO) and execute
the origin search again. Turn the
power supply OFF and then ON
if the signal type setting was
changed.
Summary of Contents for CP1H CPU UNITS - PROGRAMMING 05-2007
Page 2: ......
Page 3: ...CP1H X40D CP1H XA40D CP1H Y20DT D CP1H CPU Unit Operation Manual Revised March 2009...
Page 4: ...iv...
Page 10: ...x...
Page 18: ...xviii...
Page 22: ...xxii...
Page 34: ...xxxiv Conformance to EC Directives 6...
Page 174: ...140 CP series Expansion I O Unit Wiring Section 3 6...
Page 370: ...336 Analog I O XA CPU Units Section 5 5...
Page 552: ...518 Trouble Shooting Section 8 7...
Page 595: ...561 Sample Application Section 9 12 Network Settings Network Tab Network Settings Driver Tab...
Page 598: ...564 Sample Application Section 9 12...
Page 642: ...608 Standard Models Appendix A...
Page 652: ...618 Dimensions Diagrams Appendix B...
Page 745: ...711 Connections to Serial Communications Option Boards Appendix F Connecting to Unit...
Page 746: ...712 Connections to Serial Communications Option Boards Appendix F...
Page 776: ...742 PLC Setup Appendix G...
Page 778: ...744 Specifications for External Power Supply Expansion Appendix H...
Page 786: ...752 Revision History...