241
Pulse Outputs
Section 5-3
Independent Mode (Positioning)
Starting a Pulse Output
Note
Triangular Control
If the specified number of pulses is less than the number required just to
reach the target frequency and return to zero, the function will automatically
reduce the acceleration/deceleration time and perform triangular control
(acceleration and deceleration only.) An error will not occur.
Operation
Example
application
Frequency changes
Description
Procedure
Instruction
Settings
Output with
specified
speed
Positioning
without accel-
eration or
deceleration
Starts outputting
pulses at the speci-
fied frequency and
stops immediately
when the specified
number of pulses
has been output.
Note
The target
position
(specified
number of
pulses) can-
not be
changed dur-
ing position-
ing.
PULS(886)
↓
SPED(885)
•Number
of pulses
•Relative
or abso-
lute pulse
specifica-
tion
•Port
•“CW/
CCW” or
“Pulse +
direction”
•Indepen-
dent
•Target fre-
quency
Simple trap-
ezoidal con-
trol
Positioning
with trapezoi-
dal accelera-
tion and
deceleration
(Same rate
used for
acceleration
and decelera-
tion; no start-
ing speed)
The number
of pulses can-
not be
changed dur-
ing position-
ing.
Accelerates and
decelerates at the
same fixed rate and
stops immediately
when the specified
number of pulses
has been output.
(See note.)
Note
The target
position
(specified
number of
pulses) can-
not be
changed dur-
ing position-
ing.
PULS(886)
↓
ACC(888)
(Indepen-
dent)
•Number
of pulses
•Relative
or abso-
lute pulse
specifica-
tion
•Port
•“CW/
CCW” or
“Pulse +
direction”
•Indepen-
dent
•Accelera-
tion and
decelera-
tion rate
•Target fre-
quency
Complex
trapezoidal
control
Positioning
with trapezoi-
dal accelera-
tion and
deceleration
(Separate
rates used for
acceleration
and decelera-
tion; starting
speed)
The number
of pulses can
be changed
during posi-
tioning.
Accelerates and
decelerates at a
fixed rates. The
pulse output is
stopped when the
specified number of
pulses has been
output. (See note.)
Note
The target
position
(specified
number of
pulses) can
be changed
during posi-
tioning.
PLS2(887)
•Number
of pulses
•Relative
or abso-
lute pulse
specifica-
tion
•Port
•“CW/
CCW” or
“Pulse +
direction”
•Accelera-
tion rate
•Decelera-
tion rate
•Target fre-
quency
•Starting
frequency
Pulse frequency
Target
frequency
Specified number of
pulses (Specified with
PULS(886).)
Execution of
SPED(885)
Outputs the specified
number of pulses
and then stops.
Time
Pulse frequency
Target
frequency
Specified number of
pulses (Specified
with PULS(886).)
Acceleration/
deceleration
rate
Execution of
ACC(888)
Outputs the specified
number of pulses and
then stops.
Time
Pulse frequency
Target
frequency
Starting
frequency
Acceler-
ation
rate
Specified number
of pulses
Deceleration
rate
Execution of
PLS2(887) Target
frequency
reached.
Deceleration point
Output stops.
Stop
frequency
Time
Summary of Contents for CP1H CPU UNITS - PROGRAMMING 05-2007
Page 2: ......
Page 3: ...CP1H X40D CP1H XA40D CP1H Y20DT D CP1H CPU Unit Operation Manual Revised March 2009...
Page 4: ...iv...
Page 10: ...x...
Page 18: ...xviii...
Page 22: ...xxii...
Page 34: ...xxxiv Conformance to EC Directives 6...
Page 174: ...140 CP series Expansion I O Unit Wiring Section 3 6...
Page 370: ...336 Analog I O XA CPU Units Section 5 5...
Page 552: ...518 Trouble Shooting Section 8 7...
Page 595: ...561 Sample Application Section 9 12 Network Settings Network Tab Network Settings Driver Tab...
Page 598: ...564 Sample Application Section 9 12...
Page 642: ...608 Standard Models Appendix A...
Page 652: ...618 Dimensions Diagrams Appendix B...
Page 745: ...711 Connections to Serial Communications Option Boards Appendix F Connecting to Unit...
Page 746: ...712 Connections to Serial Communications Option Boards Appendix F...
Page 776: ...742 PLC Setup Appendix G...
Page 778: ...744 Specifications for External Power Supply Expansion Appendix H...
Page 786: ...752 Revision History...