![background image](http://html1.mh-extra.com/html/omron/cp1h-cpu-units-programming-05-2007/cp1h-cpu-units-programming-05-2007_operation-manual_742081654.webp)
620
Auxiliary Area Allocations by Function
Appendix C
Built-in Inputs
Analog Adjustment and External Analog Setting Input
Input Interrupts, Interrupt Counters 0 to 7
High-speed Counters 0 to 3
Name
Address
Description
Access
Updated
Analog Adjustment
PV
A642
Stores the value set on the analog adjuster as a hexadecimal
value (resolution: 1/256).
0000 to 00FF hex
Read-only
When analog
adjustment is
turned
External Analog
Setting Input PV
A643
Stores the value set from the external analog setting input as a
hexadecimal value (resolution: 1/256).
0000 to 00FF hex
Read-only
Interrupt counter
Counter SV
Counter PV
Interrupt counter 0
A532
A536
Interrupt counter 1
A533
A537
Interrupt counter 2
A534
A538
Interrupt counter 3
A535
A539
Interrupt counter 4
A544
A548
Interrupt counter 5
A545
A549
Interrupt counter 6
A546
A550
Interrupt counter 7
A547
A551
Name
Description
Access
Updated
Interrupt Counter
Counter SV
Used for an interrupt input in counter mode.
Sets the count value at which the interrupt task will start. The corre-
sponding interrupt task will start when the interrupt counter has
counted this number of pulses.
Read/Write
• Retained when power is
turned ON.
• Retained when opera-
tion starts.
Interrupt Counter
Counter PV
These words contain the interrupt counter PVs for interrupt inputs
operating in counter mode.
In increment mode, the counter PV starts incrementing from 0.
When the counter PV reaches the counter SV, the PV is automati-
cally reset to 0.
In decrement mode, the counter PV starts decrementing from the
counter SV. When the counter PV reaches the 0, the PV is automat-
ically reset to the SV.
Read/Write
• Retained when power is
turned ON.
• Cleared when operation
starts.
• Updated when interrupt
is generated.
Item
High-speed
counter 0
High-speed
counter 1
High-speed
counter 2
High-speed
counter 3
High-speed Counter PV
Leftmost 4 digits
A271
A273
A317
A319
Rightmost 4 digits A270
A272
A316
A318
High-speed Counter Range
Comparison Condition Met Flag
Range 1
A274.00
A275.00
A320.00
A321.00
Range 2
A274.01
A275.01
A320.01
A321.01
Range 3
A274.02
A275.02
A320.02
A321.02
Range 4
A274.03
A275.03
A320.03
A321.03
Range 5
A274.04
A275.04
A320.04
A321.04
Range 6
A274.05
A275.05
A320.05
A321.05
Range 7
A274.06
A275.06
A320.06
A321.06
Range 8
A274.07
A275.07
A320.07
A321.07
High-speed Counter Comparison In-progress Flag
A274.08
A275.08
A320.08
A321.08
High-speed Counter Overflow/Underflow Flag
A274.09
A275.09
A320.09
A321.09
High-speed Counter Count Direction
A274.10
A275.10
A320.10
A321.10
High-speed Counter Count Reset Bit
A531.00
A531.01
A531.02
A531.03
High-speed Counter Gate Flag
A531.08
A531.09
A531.10
A531.11
Summary of Contents for CP1H CPU UNITS - PROGRAMMING 05-2007
Page 2: ......
Page 3: ...CP1H X40D CP1H XA40D CP1H Y20DT D CP1H CPU Unit Operation Manual Revised March 2009...
Page 4: ...iv...
Page 10: ...x...
Page 18: ...xviii...
Page 22: ...xxii...
Page 34: ...xxxiv Conformance to EC Directives 6...
Page 174: ...140 CP series Expansion I O Unit Wiring Section 3 6...
Page 370: ...336 Analog I O XA CPU Units Section 5 5...
Page 552: ...518 Trouble Shooting Section 8 7...
Page 595: ...561 Sample Application Section 9 12 Network Settings Network Tab Network Settings Driver Tab...
Page 598: ...564 Sample Application Section 9 12...
Page 642: ...608 Standard Models Appendix A...
Page 652: ...618 Dimensions Diagrams Appendix B...
Page 745: ...711 Connections to Serial Communications Option Boards Appendix F Connecting to Unit...
Page 746: ...712 Connections to Serial Communications Option Boards Appendix F...
Page 776: ...742 PLC Setup Appendix G...
Page 778: ...744 Specifications for External Power Supply Expansion Appendix H...
Page 786: ...752 Revision History...