169
Data Memory Area (D)
Section 4-14
Forcing Bit Status
Bits in the DM Area cannot be force-set or force-reset.
Indirect Addressing
Words in the DM Area can be indirectly addressed in two ways: binary-mode
and BCD-mode.
Binary-mode Addressing (@D)
When a “@” character is input before a DM address, the content of that DM
word is treated as binary and the instruction will operate on the DM word at
that binary address. The entire DM Area (D0 to D32767) can be indirectly
addressed with hexadecimal values 0000 to 7FFF.
BCD-mode Addressing (
*
D)
When a “
*
” character is input before a DM address, the content of that DM
word is treated as BCD and the instruction will operate on the DM word at that
BCD address. Only part of the DM Area (D0 to D09999) can be indirectly
addressed with BCD values 0000 to 9999.
DM Area Allocation to
Special I/O Units
Parts of the DM Area are allocated to Special I/O Units and CPU Bus Units for
functions such as initial Unit settings. The timing for data transfers is different
for these Units, but may occur at any of the three following times.
1,2,3...
1.
Transfer data when the PLC’s power is cycled or the Unit is restarted.
2.
Transfer data once each cycle.
3.
Transfer data when required.
Refer to the Unit’s operation manual for details on data transfer timing.
Special I/O Units (D20000 to D29599)
Each Special I/O Unit is allocated 100 words based on unit numbers 0 to 95.
Refer to the Unit’s operation manual for details on the function of these words.
@D100
D256
0100
▲
Address actually used.
*
D100
D100
0100
▲
Address actually used.
DM Area for Special I/O Units
(100 words/Unit)
CPU Unit
Special I/O Unit
Data trans-
ferred to the
Special I/O
unit when the
PLC is turned
ON or the Unit
is restarted.
Data trans-
ferred to the
CPU Unit at
cyclic refresh-
ing or when
necessary.
Summary of Contents for CP1H CPU UNITS - PROGRAMMING 05-2007
Page 2: ......
Page 3: ...CP1H X40D CP1H XA40D CP1H Y20DT D CP1H CPU Unit Operation Manual Revised March 2009...
Page 4: ...iv...
Page 10: ...x...
Page 18: ...xviii...
Page 22: ...xxii...
Page 34: ...xxxiv Conformance to EC Directives 6...
Page 174: ...140 CP series Expansion I O Unit Wiring Section 3 6...
Page 370: ...336 Analog I O XA CPU Units Section 5 5...
Page 552: ...518 Trouble Shooting Section 8 7...
Page 595: ...561 Sample Application Section 9 12 Network Settings Network Tab Network Settings Driver Tab...
Page 598: ...564 Sample Application Section 9 12...
Page 642: ...608 Standard Models Appendix A...
Page 652: ...618 Dimensions Diagrams Appendix B...
Page 745: ...711 Connections to Serial Communications Option Boards Appendix F Connecting to Unit...
Page 746: ...712 Connections to Serial Communications Option Boards Appendix F...
Page 776: ...742 PLC Setup Appendix G...
Page 778: ...744 Specifications for External Power Supply Expansion Appendix H...
Page 786: ...752 Revision History...