430
Temperature Sensor Units
Section 7-5
Part Names
Temperature Sensor Units:
CP1W-TS
and CPM1A-TS
(1)
Temperature Sensor Input Terminals
Used to connect temperature sensors such as thermocouples or plati-
num resistance thermometers.
(2)
DIP Switch
Used to set the temperature unit (
°
C or
°
F) and the number of decimal
places used.
(3)
Rotary Switch
Used to set the temperature input range. Make the setting according to
the specifications of the temperature sensors that are connected.
(4)
Expansion I/O Connecting Cable
Connected to the expansion connector of a CP1H CPU Unit or a CP-
series Expansion Unit or Expansion I/O Unit.The cable is included with
the Temperature Sensor Unit and cannot be removed.
Note
Do not touch the cables during operation. Static electricity may
cause operating errors.
(5)
Expansion Connector
Used for connecting CP-series Expansion Units or Expansion I/O Units.
Main Specifications
Note
Accuracy for a K-type sensor at
−
100
°
C or less is ±4
°
C ±1 digit max.
(5) Expansion Connector
(1) Temperature Sensor Input Terminals
(4) Expansion I/O
Connector Cable
(3) Rotary Switch
(2) DIP Switch
Item
CP1W-TS001
CPM1A-TS001
CP1W-TS002
CPM1A-TS002
CP1W-TS101
CPM1A-TS101
CP1W-TS102
CPM1A-TS102
Temperature sensors
Thermocouples
Platinum resistance thermometer
Switchable between K and J, but same type
must be used for all inputs.
Switchable between Pt100 and JPt100, but
same type must be used for all inputs.
Number of inputs
2
4
2
4
Allocated input words
2
4
2
4
Max. number of Units
3
1
3
1
Accuracy
(The larger of
±
0.5% of converted value or
±
2
°
C)
±
1 digit max. (See note.)
(The larger of
±
0.5% of converted value or
±
1
°
C)
±
1 digit max.
Conversion time
250 ms for 2 or 4 input points
Converted temperature data
16-bit binary data (4-digit hexadecimal)
Isolation
Photocouplers between all temperature input signals
Current consumption
5 VDC: 40 mA max., 24 VDC: 59 mA max.
5 VDC: 54 mA max., 24 VDC: 73 mA max.
Summary of Contents for CP1H CPU UNITS - PROGRAMMING 05-2007
Page 2: ......
Page 3: ...CP1H X40D CP1H XA40D CP1H Y20DT D CP1H CPU Unit Operation Manual Revised March 2009...
Page 4: ...iv...
Page 10: ...x...
Page 18: ...xviii...
Page 22: ...xxii...
Page 34: ...xxxiv Conformance to EC Directives 6...
Page 174: ...140 CP series Expansion I O Unit Wiring Section 3 6...
Page 370: ...336 Analog I O XA CPU Units Section 5 5...
Page 552: ...518 Trouble Shooting Section 8 7...
Page 595: ...561 Sample Application Section 9 12 Network Settings Network Tab Network Settings Driver Tab...
Page 598: ...564 Sample Application Section 9 12...
Page 642: ...608 Standard Models Appendix A...
Page 652: ...618 Dimensions Diagrams Appendix B...
Page 745: ...711 Connections to Serial Communications Option Boards Appendix F Connecting to Unit...
Page 746: ...712 Connections to Serial Communications Option Boards Appendix F...
Page 776: ...742 PLC Setup Appendix G...
Page 778: ...744 Specifications for External Power Supply Expansion Appendix H...
Page 786: ...752 Revision History...