639
Appendix D
Auxiliary Area Allocations by Address
Read-only Area (Set by System)
Address
Name
Function
Settings
Status
after
mode
change
Status
at star-
tup
Write
timing
Related
flags, set-
tings
Words
Bits
A0
---
10-ms Incre-
menting Free
Running
Timer
This word contains the system timer
used after the power is turned ON.
A value of 0000 hex is set when the
power is turned ON and this value is
automatically incremented by 1 every
10 ms. The value returns to 0000 hex
after reaching FFFF hex
(655,350 ms), and then continues to
be automatically incremented by 1
every 10 ms.
Note:
The timer will continue to be
incremented when the operat-
ing mode is switched to RUN
mode.
Example: The interval can be
counted between processing A and
processing B without requiring timer
instructions. This is achieved by
calculating the difference between
the value in A0 for processing A and
the value in A0 for processing B. The
interval is counted in 10 ms units.
---
Retained
Cleared
Every
10 ms after
power is
turned ON
---
A1
---
100-ms Incre-
menting Free
Running
Timer
This word contains the system timer
used after the power is turned ON.
A value of 0000 hex is set when the
power is turned ON and this value is
automatically incremented by 1 every
100 ms. The value returns to 0000
hex after reaching FFFF hex
(6,553,500 ms), and then continues
to be automatically incremented by 1
every 100 ms.
Note:
The timer will continue to be
incremented when the operat-
ing mode is switched to RUN
mode.
Example: The interval can be
counted between processing A and
processing B without requiring timer
instructions. This is achieved by
calculating the difference between
the value in A0 for processing A and
the value in A0 for processing B. The
interval is counted in 100 ms units.
---
Retained
Cleared
Every
100 ms
after power
is turned
ON
---
A90 to
A93
All
User Program
Date
These words contain in BCD the
date and time that the user program
was last overwritten.
A90.00 to A90.07:
Seconds (00 to 59)
A90.08 to A90.15:
Minutes (00 to 59)
A91.00 to A91.07: Hour (00 to 23)
A91.08 to A91.15:
Day of month (01 to 31)
A92.00 to A92.07: Month (01 to 12)
A92.08 to A92.15: Year (00 to 99)
A93.00 to A93.07: Day of the week
(00: Sunday, 01: Monday, 02: Tues-
day, 03: Wednesday, 04: Thursday,
05: Friday, 06: Saturday)
---
Retained
Retained ---
---
Summary of Contents for CP1H CPU UNITS - PROGRAMMING 05-2007
Page 2: ......
Page 3: ...CP1H X40D CP1H XA40D CP1H Y20DT D CP1H CPU Unit Operation Manual Revised March 2009...
Page 4: ...iv...
Page 10: ...x...
Page 18: ...xviii...
Page 22: ...xxii...
Page 34: ...xxxiv Conformance to EC Directives 6...
Page 174: ...140 CP series Expansion I O Unit Wiring Section 3 6...
Page 370: ...336 Analog I O XA CPU Units Section 5 5...
Page 552: ...518 Trouble Shooting Section 8 7...
Page 595: ...561 Sample Application Section 9 12 Network Settings Network Tab Network Settings Driver Tab...
Page 598: ...564 Sample Application Section 9 12...
Page 642: ...608 Standard Models Appendix A...
Page 652: ...618 Dimensions Diagrams Appendix B...
Page 745: ...711 Connections to Serial Communications Option Boards Appendix F Connecting to Unit...
Page 746: ...712 Connections to Serial Communications Option Boards Appendix F...
Page 776: ...742 PLC Setup Appendix G...
Page 778: ...744 Specifications for External Power Supply Expansion Appendix H...
Page 786: ...752 Revision History...