267
Pulse Outputs
Section 5-3
Once the origin has been detected in an origin search, the number of pulses
specified in the origin compensation is output, the current position is reset to
0, and the pulse output's No-origin Flag is turned OFF.
Setting range: 80000000 to 7FFFFFFF hex (
−
2,147,483,648 to
2,147,483,647) pulses
I/O Settings
Limit Input Signal Type (NC/NO)
Specifies the type of input signal (normally closed or normally open) being
used for the limit inputs.
0: NC
1: NO
Origin Proximity Input Signal Type (NC/NO)
Specifies the type of input signal (normally closed or normally open) being
used for the Origin Proximity Input Signal.
0: NC
1: NO
Origin Input Signal Type (NC/NO)
Specifies the type of input signal (normally closed or normally open) being
used for the Origin Input Signal.
0: NC
1: NO
Positioning Monitor Time
When the operating mode is set to mode 2, this setting specifies how long to
wait (in ms) for the Positioning Completed Signal after the positioning opera-
tion has been completed, i.e., the pulse output has been completed. A Posi-
tioning Timeout Error (error code 0300) will be generated if the motor driver's
Positioning Completed Signal does not come ON within the specified time.
Setting range: 0000 to 270F hex (0 to 9,999 ms)
The actual monitoring time will be the Positioning Monitor Time rounded up to
the nearest 10-ms unit + 10 ms max.
If the Positioning Monitor Time is set to 0, the function will be disabled and the
Unit will continue waiting for the Positioning Completed Signal to come ON. (A
Positioning Timeout Error will not be generated.)
Executing an Origin Search
Execute ORG(889) in the ladder program to perform an origin search with the
specified parameters.
Restrictions
The motor can be moved even if the origin position has not been determined
with the origin search function, but positioning operations will be limited as fol-
lows:
P
C
ORG(889)
P: Port specifier
Pulse output 0: #0000
Pulse output 1: #0001
Pulse output 2: #0002
Pulse output 3: #0003
C: Control data; Origin search and CW/CCW method: #0000
Origin search and pulse + direction method: #0001
Function
Operation
Origin return
Cannot be used.
Summary of Contents for CP1H CPU UNITS - PROGRAMMING 05-2007
Page 2: ......
Page 3: ...CP1H X40D CP1H XA40D CP1H Y20DT D CP1H CPU Unit Operation Manual Revised March 2009...
Page 4: ...iv...
Page 10: ...x...
Page 18: ...xviii...
Page 22: ...xxii...
Page 34: ...xxxiv Conformance to EC Directives 6...
Page 174: ...140 CP series Expansion I O Unit Wiring Section 3 6...
Page 370: ...336 Analog I O XA CPU Units Section 5 5...
Page 552: ...518 Trouble Shooting Section 8 7...
Page 595: ...561 Sample Application Section 9 12 Network Settings Network Tab Network Settings Driver Tab...
Page 598: ...564 Sample Application Section 9 12...
Page 642: ...608 Standard Models Appendix A...
Page 652: ...618 Dimensions Diagrams Appendix B...
Page 745: ...711 Connections to Serial Communications Option Boards Appendix F Connecting to Unit...
Page 746: ...712 Connections to Serial Communications Option Boards Appendix F...
Page 776: ...742 PLC Setup Appendix G...
Page 778: ...744 Specifications for External Power Supply Expansion Appendix H...
Page 786: ...752 Revision History...