93
Computing the Cycle Time
Section 2-7
4: I/O Refreshing
5: Peripheral Servicing
Details
Processing time and fluctuation cause
CPU Unit built-
in I/O and I/O
on CP-series
Expansion
Units and
Expansion I/O
Units
Outputs from the CPU Unit to the actual
outputs are refreshed first for each Unit,
and then inputs.
I/O refresh time for each Unit multiplied by the number of
Units used.
CJ-series Spe-
cial I/O Units
Words allocated in CIO Area
I/O refresh time for each Unit multiplied by the number of
Units used.
Unit- specific
data
Example: CompoBus/S
remote I/O
CJ-series CPU
Bus Units
Words allocated in CIO and DM Areas
I/O refresh time for each Unit multiplied by the number of
Units used.
Unit- specific
data
Examples:
• Data links for Control-
ler Link Units
• DeviceNet remote I/O
• Send/receive data for
protocol macros
• Socket services for
specific control bits for
Ethernet Units
Details
Processing time and fluctuation cause
Services events for CJ-series Special I/O
Units.
Note
Peripheral servicing does not include
I/O refreshing,
If a uniform peripheral servicing time hasn’t been set in the PLC Setup for
this servicing, 4% of the previous cycle’s cycle time (calculated in step (3))
will be allowed for peripheral servicing.
If a uniform peripheral servicing time has been set in the PLC Setup, servic-
ing will be performed for the set time. Servicing will be performed for at
least 0.1 ms, however, whether the peripheral servicing time is set or not.
If no Units are mounted, the servicing time is 0 ms.
Services events for CJ-series CPU Bus
Units.
Note
Peripheral servicing does not include
I/O refreshing.
Services USB port.
If a uniform peripheral servicing time hasn’t been set in the PLC Setup for
this servicing, 4% of the previous cycle’s cycle time (calculated in step (3))
will be allowed for peripheral servicing.
If a uniform peripheral servicing time has been set in the PLC Setup, servic-
ing will be performed for the set time. Servicing will be performed for at
least 0.1 ms, however, whether the peripheral servicing time is set or not.
If the ports are not connected, the servicing time is 0 ms.
Services serial ports
Services communications ports.
If a uniform peripheral servicing time hasn’t been set in the PLC Setup for
this servicing, 4% of the previous cycle’s cycle time (calculated in step (3))
will be allowed for peripheral servicing.
If a uniform peripheral servicing time has been set in the PLC Setup, servic-
ing will be performed for the set time. Servicing will be performed for at
least 0.1 ms, however, whether the peripheral servicing time is set or not.
If no communications ports are used, the servicing time is 0 ms.
Services built-in flash memory access.
If a uniform peripheral servicing time hasn’t been set in the PLC Setup for
this servicing, 4% of the previous cycle’s cycle time (calculated in step (3))
will be allowed for peripheral servicing.
If a uniform peripheral servicing time has been set in the PLC Setup, servic-
ing will be performed for the set time. Servicing will be performed for at
least 0.1 ms, however, whether the peripheral servicing time is set or not.
If there is no access, the servicing time is 0 ms.
Serves Memory Cassette access.
Summary of Contents for CP1H CPU UNITS - PROGRAMMING 05-2007
Page 2: ......
Page 3: ...CP1H X40D CP1H XA40D CP1H Y20DT D CP1H CPU Unit Operation Manual Revised March 2009...
Page 4: ...iv...
Page 10: ...x...
Page 18: ...xviii...
Page 22: ...xxii...
Page 34: ...xxxiv Conformance to EC Directives 6...
Page 174: ...140 CP series Expansion I O Unit Wiring Section 3 6...
Page 370: ...336 Analog I O XA CPU Units Section 5 5...
Page 552: ...518 Trouble Shooting Section 8 7...
Page 595: ...561 Sample Application Section 9 12 Network Settings Network Tab Network Settings Driver Tab...
Page 598: ...564 Sample Application Section 9 12...
Page 642: ...608 Standard Models Appendix A...
Page 652: ...618 Dimensions Diagrams Appendix B...
Page 745: ...711 Connections to Serial Communications Option Boards Appendix F Connecting to Unit...
Page 746: ...712 Connections to Serial Communications Option Boards Appendix F...
Page 776: ...742 PLC Setup Appendix G...
Page 778: ...744 Specifications for External Power Supply Expansion Appendix H...
Page 786: ...752 Revision History...