557
Trouble Shooting
Section 9-11
9-11-2 Trouble-shooting with Indicators and Error Code Display
ERR
Indicator
Error
Probably Cause
Error code
(hex)
Correction
Lit
CPU Unit service
monitoring error
Service from the CPU
Unit was not com-
pleted within the fixed
interval. The monitor-
ing time is normally
11s.
0002
Check and correct the CPU Unit’s operating
environment.
Check whether the related DIP SW is on.
Refer to
9-8-2 Installation and Removing
.
Note
Recovery is possible for this error.
When operation is restored, it will
return to normal.
Two option boards
installed
Two option boards
have been installed on
the CPU Unit.
---
Uninstall the Ethernet Option Board in one
serial port of the CPU Unit and restart the
CPU unit.
Option board error
An error occurred in
the Ethernet Option
Board.
0601
Restart the CPU Unit. Replace the Ethernet
Option Board if the error recurs.
Option board
memory error
An error occurred in
the Unit’s non-volatile
memory itself. This
error will occur while
writing or reading the
error log, system
setup, identity data,
MAC ID.
0602
Restart the CPU Unit. Replace the Ethernet
Option Board if the error recurs.
Flashing
CPU Unit memory
error
A parity error occurred
during an operation
such as reading the
routing tables.
0012
Register the routing table in the CPU Unit
again and restart the CPU Unit. Replace the
CPU Unit if the error recurs.
CPU Unit pro-
tected
CPU Unit protected.
0013
Remove protection from CPU Unit memory.
CPU Unit fatal
error
A fatal error occurred
in the CPU Unit.
0015
Eliminate the cause of the error in the CPU
Unit.
CPU Unit power
failure
CPU Unit power OFF,
Ethernet Option Board
is still running.
0014
Restart the PLC (Power OFF and power ON).
IP address setting
error
The IP address is set
incorrectly.
021A
Correct the IP address. Do not set any of
the following IP addresses.
•
Host IDs that are all 0 or all 1.
•
Network IDs that are all 0 or all 1.
•
Subnetwork IDs that are all 1.
•
Addresses beginning with 127 (7F hex).
IP address table
error
The IP address table
is set incorrectly.
021A
Correct the IP address table.
IP Router table
setting error
The IP Router table is
set incorrectly.
021A
Correct the IP Router table.
Summary of Contents for CP1H CPU UNITS - PROGRAMMING 05-2007
Page 2: ......
Page 3: ...CP1H X40D CP1H XA40D CP1H Y20DT D CP1H CPU Unit Operation Manual Revised March 2009...
Page 4: ...iv...
Page 10: ...x...
Page 18: ...xviii...
Page 22: ...xxii...
Page 34: ...xxxiv Conformance to EC Directives 6...
Page 174: ...140 CP series Expansion I O Unit Wiring Section 3 6...
Page 370: ...336 Analog I O XA CPU Units Section 5 5...
Page 552: ...518 Trouble Shooting Section 8 7...
Page 595: ...561 Sample Application Section 9 12 Network Settings Network Tab Network Settings Driver Tab...
Page 598: ...564 Sample Application Section 9 12...
Page 642: ...608 Standard Models Appendix A...
Page 652: ...618 Dimensions Diagrams Appendix B...
Page 745: ...711 Connections to Serial Communications Option Boards Appendix F Connecting to Unit...
Page 746: ...712 Connections to Serial Communications Option Boards Appendix F...
Page 776: ...742 PLC Setup Appendix G...
Page 778: ...744 Specifications for External Power Supply Expansion Appendix H...
Page 786: ...752 Revision History...