527
FINS Communications
Section 9-5
9-5-2
Overview of FINS Communication Service
Basic Functions
FINS commands can be received from other PLCs or computers on the same
Ethernet network by executing SEND(090), RECV(098), or CMND
(490) instructions in the ladder diagram program. This enables various control
operations such as the reading and writing of I/O memory between PLCs,
mode changes, and file memory operations.
Executing, from the host computer, FINS commands with UDP/IP or TCP/IP
headers enables various control operations, such as the reading and writing
of I/O memory between PLCs, mode changes, and file memory operations.
For example, it is possible to connect online via Ethernet from FINS communi-
cations applications such as the CX-Programmer, and to perform remote pro-
gramming and monitoring.
Upgraded Functions
With the CP1W-CIF41, the following functions have been upgraded.
• The FINS communications service can be executed not only with UDP/IP
but also with TCP/IP, and it is even possible to use FINS communications
with both UDP/IP and TCP/IP together on the same network. Using
TCP/IP makes FINS communications highly reliable.
• Even if the IP address and UDP port number of the host computer (a
DHCP client computer) are changed, it is still possible for the host com-
puter to send FINS commands to PLCs on the Ethernet network and to
receive responses. When UDP is used, either the automatic generation
(dynamic) method or the IP address table method must be selected for IP
address conversion. When TCP is used, changes in IP address and TCP
port numbers are handled automatically.
• Multiple FINS applications (CX-Programmer and user-created application
programs) at the same computer can be connected online to a PLC via
Ethernet (using either TCP/IP or UDP/IP).
Note
The message service does not guarantee that a message will reach the desti-
nation node. A message may be lost during transmission due to factors such
as noise. To prevent this from occurring when using message services, it is
common to set up retry processing at the node from which instructions are
issued. With the SEND(090), RECV(098), and CMND(490) instructions, retry
processing is executed automatically by specifying the number of retries, so
specify a number other than 0.
Ethernet
Ethernet Option Board
Ethernet Option Board
Ethernet Option Board
IP
UDP or TCP
FINS
CP1L/H CPU Unit
Summary of Contents for CP1H CPU UNITS - PROGRAMMING 05-2007
Page 2: ......
Page 3: ...CP1H X40D CP1H XA40D CP1H Y20DT D CP1H CPU Unit Operation Manual Revised March 2009...
Page 4: ...iv...
Page 10: ...x...
Page 18: ...xviii...
Page 22: ...xxii...
Page 34: ...xxxiv Conformance to EC Directives 6...
Page 174: ...140 CP series Expansion I O Unit Wiring Section 3 6...
Page 370: ...336 Analog I O XA CPU Units Section 5 5...
Page 552: ...518 Trouble Shooting Section 8 7...
Page 595: ...561 Sample Application Section 9 12 Network Settings Network Tab Network Settings Driver Tab...
Page 598: ...564 Sample Application Section 9 12...
Page 642: ...608 Standard Models Appendix A...
Page 652: ...618 Dimensions Diagrams Appendix B...
Page 745: ...711 Connections to Serial Communications Option Boards Appendix F Connecting to Unit...
Page 746: ...712 Connections to Serial Communications Option Boards Appendix F...
Page 776: ...742 PLC Setup Appendix G...
Page 778: ...744 Specifications for External Power Supply Expansion Appendix H...
Page 786: ...752 Revision History...