193
Interrupt Functions
Section 5-1
Operation
When execution condition W0.00 goes ON, MSKS(690) is executed to enable
CIO 0.00 as an up-differentiated input interrupt.
If CIO 0.00 goes from OFF to ON (up-differentiation), processing of the cyclic
task that is currently being executed will be interrupted and processing of
interrupt task 140 will start. When the interrupt task processing is completed,
processing of the interrupted ladder program will restart.
Restrictions
Inputs cannot be used for input interrupts when they are being used as gen-
eral-purpose (normal) inputs or quick-response inputs.
5-1-3
Input Interrupts (Counter Mode)
Overview
This function counts up-differentiated or down-differentiated input signals and
executes an interrupt task when the count reaches the set value.
• The counter-mode input interrupts use the same input terminals as the
direct-mode input interrupts. Refer to
5-1-2 Input Interrupts (Direct Mode)
for details.
• The counter input mode can be set to up or down (incrementing or decre-
menting) with MSKS(690).
• The counter-mode input interrupts start the same interrupt tasks (140 to
147) as the direct-mode input interrupts.
• The maximum input response frequency is 5 kHz total for all counter-
mode input interrupts.
Relationship of Input Bits,
Task Numbers, and
Counters
Note
*Input interrupts 6 and 7 are not supported by the Y CPU Units.
W0.00
0.00
MSKS(690) executed
Cyclic task processing
Interrupt
task 140
processing
Processing
interrupted
Cyclic task
processing
Processing
interrupted
Interrupt
task 140
processing
Input bits
Function
Counter words
X/XA
CPU
Unit
Y CPU
Unit
Input interrupt
number
Interrupt task
number
SV
(0000 to FFFF)
PV
0.00
0.00
Input interrupt 0
140
A532
A536
0.01
0.01
Input interrupt 1
141
A533
A537
0.02
1.00
Input interrupt 2
142
A534
A538
0.03
1.01
Input interrupt 3
143
A535
A539
1.00
1.02
Input interrupt 4
144
A544
A548
1.01
1.03
Input interrupt 5
145
A545
A549
1.02
---
Input interrupt 6
146 (see note) A546
A550
1.03
---
Input interrupt 7
147 (see note) A547
A551
Summary of Contents for CP1H CPU UNITS - PROGRAMMING 05-2007
Page 2: ......
Page 3: ...CP1H X40D CP1H XA40D CP1H Y20DT D CP1H CPU Unit Operation Manual Revised March 2009...
Page 4: ...iv...
Page 10: ...x...
Page 18: ...xviii...
Page 22: ...xxii...
Page 34: ...xxxiv Conformance to EC Directives 6...
Page 174: ...140 CP series Expansion I O Unit Wiring Section 3 6...
Page 370: ...336 Analog I O XA CPU Units Section 5 5...
Page 552: ...518 Trouble Shooting Section 8 7...
Page 595: ...561 Sample Application Section 9 12 Network Settings Network Tab Network Settings Driver Tab...
Page 598: ...564 Sample Application Section 9 12...
Page 642: ...608 Standard Models Appendix A...
Page 652: ...618 Dimensions Diagrams Appendix B...
Page 745: ...711 Connections to Serial Communications Option Boards Appendix F Connecting to Unit...
Page 746: ...712 Connections to Serial Communications Option Boards Appendix F...
Page 776: ...742 PLC Setup Appendix G...
Page 778: ...744 Specifications for External Power Supply Expansion Appendix H...
Page 786: ...752 Revision History...