388
Connecting CP-series Expansion Units and Expansion I/O Units
Section 7-1
7-1
Connecting CP-series Expansion Units and Expansion I/O
Units
CP-series Expansion Units and Expansion I/O Units can be connected to the
CP1H. The combined maximum number of Expansion Units and Expansion I/
O Units that can be connected is seven. CPM1A-AD041 Analog Input Units,
CPM1A-DA041 Analog Output Units, and CPM1A-TS002 and CPM1A-TS102
Temperature Sensor Units are allocated four words in the I/O area, however,
so when any of these Units is included the total number of Expansion Units
and Expansion I/O Units must be reduced.
Number of I/O Words
Unit name
Model
Current
consumption (mA)
I/O words
5 VDC
24 VDC
Input
Output
Expansion
Units
Analog Input Unit
CP1W-AD041
CPM1A-AD041
100
90
4
2
Analog Output Unit
CP1W-DA041
CPM1A-DA041
80
124
---
4
Analog I/O Unit
CPM1A-MAD01
66
66
2
1
CP1W-MAD11
CPM1A-MAD11
83
110
Temperature Control Unit
CP1W-TS001
CPM1A-TS001
40
59
2
---
CP1W-TS101
CPM1A-TS101
54
73
CP1W-TS002
CPM1A-TS002
40
59
4
---
CP1W-TS102
CPM1A-TS102
54
73
CompoBus/S I/O Link Unit
CP1W-SRT21
CPM1A-SRT21
29
---
1
1
DeviceNet I/O Link Unit
CPM1A-DRT21
48
---
2
2
Expansion
I/O Units
40-point I/O Unit
CP1W-40EDR
CPM1A-40EDR
80
90
2
2
CP1W-40EDT
CPM1A-40EDT
160
---
CP1W-40EDT1
CPM1A-40EDT1
160
---
32-point Output Unit
CP1W-32ER
49
131
---
2
CP1W-32ET
113
---
CP1W-32ET1
113
---
20-point I/O Unit
CP1W-20EDR1
CPM1A-20EDR1
103
44
1
1
CP1W-20EDT
CPM1A-20EDT
130
---
CP1W-20EDT1
CPM1A-20EDT1
130
---
16-point Output Unit
CP1W-16ER
CPM1A-16ER
42
90
---
2
CP1W-16ET
76
---
CP1W-16ET1
76
---
8-point Input Unit
CP1W-8ED
CPM1A-8ED
18
---
1
---
8-point Output Unit
CP1W-8ER
CPM1A-8ER
26
44
---
1
CP1W-8ET
CPM1A-8ET
75
---
CP1W-8ET1
CPM1A-8ET1
75
---
Note
CP1W-32ER/32ET/32ET1’s maximum number of simultaneously ON points is 24 (75%).
Summary of Contents for CP1H CPU UNITS - PROGRAMMING 05-2007
Page 2: ......
Page 3: ...CP1H X40D CP1H XA40D CP1H Y20DT D CP1H CPU Unit Operation Manual Revised March 2009...
Page 4: ...iv...
Page 10: ...x...
Page 18: ...xviii...
Page 22: ...xxii...
Page 34: ...xxxiv Conformance to EC Directives 6...
Page 174: ...140 CP series Expansion I O Unit Wiring Section 3 6...
Page 370: ...336 Analog I O XA CPU Units Section 5 5...
Page 552: ...518 Trouble Shooting Section 8 7...
Page 595: ...561 Sample Application Section 9 12 Network Settings Network Tab Network Settings Driver Tab...
Page 598: ...564 Sample Application Section 9 12...
Page 642: ...608 Standard Models Appendix A...
Page 652: ...618 Dimensions Diagrams Appendix B...
Page 745: ...711 Connections to Serial Communications Option Boards Appendix F Connecting to Unit...
Page 746: ...712 Connections to Serial Communications Option Boards Appendix F...
Page 776: ...742 PLC Setup Appendix G...
Page 778: ...744 Specifications for External Power Supply Expansion Appendix H...
Page 786: ...752 Revision History...