Web Browser Setup and Display
Section 9-10
9-10-3 System
System Format
Item
Contents
Default
IP Address
Set the local IP address for the Ethernet Option Board.
•
Setting range: 00.00.00.00 to 223.255.255.255
192.168.250.1
Subnet Mask
Set the subnet mask for the Ethernet Option Board.
This is required if a method other than the IP address table method is
used for address conversion.
255.255.255.0
FINS Node Address
Set the local FINS node address for the Ethernet Option Board.
•
Setting range: 1 to 254
1
FINS/UDP Port
Specify the local UDP port number to be used for the FINS communica-
tions service. The UDP port number is the number used for UDP identi-
fication of the application layer (i.e., FINS communications service).
•
Setting range: 1 to 65,535
9,600
FINS/TCP Port
Specify the local TCP port number to be used for the FINS communica-
tions service. The TCP port number is the number used for TCP identifi-
cation of the application layer (i.e., the FINS communications service in
this case).
•
Setting range: 1 to 65,535
Note
Make the settings so that TCP port number 80 for HTTP does not
overlap.
The port number setting only has an effect on the FINS/TCP
server function, not on the FINS/TCP client function. FINS/TCP
client port will switch from 3000 to 65535 automatically for con-
nection.
9,600
Use Input Port No.
Check this checkbox, if you want the user defined port number for UDP
or TCP to be in effect.
Unchecked
Address Conversion
Mode
Select any of the following as the method for finding and converting IP
addresses from FINS node addresses. (Enabled for FINS/UDP only.)
• Auto (dynamic): Automatic generation (dynamic)
•
Auto (static): Automatic generation (static)
•
Manual: IP address table method
•
Auto & Manual: Combined method
Auto (dynamic)
FINS/UDP Option
Select to dynamically change the remote (destination) IP address for
FINS/UDP or not. To prohibit dynamic changes, check the second box.
Change
dynamically
Summary of Contents for CP1H CPU UNITS - PROGRAMMING 05-2007
Page 2: ......
Page 3: ...CP1H X40D CP1H XA40D CP1H Y20DT D CP1H CPU Unit Operation Manual Revised March 2009...
Page 4: ...iv...
Page 10: ...x...
Page 18: ...xviii...
Page 22: ...xxii...
Page 34: ...xxxiv Conformance to EC Directives 6...
Page 174: ...140 CP series Expansion I O Unit Wiring Section 3 6...
Page 370: ...336 Analog I O XA CPU Units Section 5 5...
Page 552: ...518 Trouble Shooting Section 8 7...
Page 595: ...561 Sample Application Section 9 12 Network Settings Network Tab Network Settings Driver Tab...
Page 598: ...564 Sample Application Section 9 12...
Page 642: ...608 Standard Models Appendix A...
Page 652: ...618 Dimensions Diagrams Appendix B...
Page 745: ...711 Connections to Serial Communications Option Boards Appendix F Connecting to Unit...
Page 746: ...712 Connections to Serial Communications Option Boards Appendix F...
Page 776: ...742 PLC Setup Appendix G...
Page 778: ...744 Specifications for External Power Supply Expansion Appendix H...
Page 786: ...752 Revision History...